Smart Cities

Chapter 10
Smart Energy, Water, Waste and Utility Systems

Bachelors Program in Construction Technology
Smart Cities   •   Bachelor

Smart Energy, Water, Waste and Utility Systems

Introduction

Cities depend on interconnected utility systems that provide electricity, heating and cooling, potable water, wastewater treatment, solid-waste collection, telecommunications and public services. Conventional utility networks generally operate as separate, centrally managed systems. Smart-city development seeks to make these systems more observable, responsive, efficient and resilient by combining physical infrastructure with sensors, communications, data platforms, automation and informed human decision-making.

For construction and infrastructure professionals, “smart” does not simply mean installing digital devices. A smart utility system must solve a defined operational problem, produce reliable information, support appropriate decisions and deliver measurable improvements in cost, resource efficiency, safety, environmental performance or service quality. It must also remain maintainable, secure and accessible to all users.

This chapter examines smart grids, distributed energy, renewable-energy integration, demand response, smart metering, water monitoring and leakage control, circular waste systems, and coordinated utility management. The emphasis is on application: how systems are designed, integrated and evaluated in the built environment.

Learning Objectives

By the end of this chapter, students should be able to:

  1. Explain the architecture and operating principles of smart electricity grids.
  2. Distinguish centralized generation, distributed energy resources and microgrids.
  3. Analyze renewable integration, energy storage and demand-response strategies.
  4. Describe the functions, benefits and limitations of smart meters.
  5. Apply basic water-balance and leakage-control concepts.
  6. Explain circular approaches to municipal solid waste management.
  7. Evaluate how common data platforms coordinate multiple utility systems.
  8. Identify technical, economic, ethical, cybersecurity and governance risks.

1. The Utility System as an Integrated Urban Service

A utility system has four broad layers:

  • Physical layer: generators, substations, pipes, pumps, tanks, treatment plants, roads, bins and buildings.
  • Sensing and control layer: meters, pressure sensors, flow meters, cameras, controllers and actuators.
  • Communication layer: wired or wireless networks that transmit measurements and commands.
  • Application and governance layer: software, operators, regulations, tariffs, maintenance procedures and public accountability.

The value of smart infrastructure arises from the interaction of these layers. A pressure sensor alone does not reduce water loss; it must be connected to an analytical process that detects abnormal pressure, identifies a likely failure and initiates inspection or control. Similarly, a smart electricity meter does not automatically reduce consumption unless information, pricing or automation changes customer or system behaviour.

A useful systems perspective is to evaluate each proposed intervention through five questions:

  1. What service problem is being addressed?
  2. What data are required, and how accurate and timely must they be?
  3. What decision or control action follows from the data?
  4. Who owns, operates and maintains the system?
  5. How will benefits, risks and equity impacts be measured?

2. Smart Electricity Grids

2.1 From conventional grids to smart grids

A conventional power system typically follows a one-way chain: large generators produce electricity, transmission networks transport it, distribution networks deliver it, and customers consume it. A smart grid retains this physical structure but adds two-way power flows, two-way communication, automated control and improved visibility.

A smart grid can therefore be understood as an electricity network that integrates generation, consumers, storage and digital control to improve reliability, efficiency, flexibility and sustainability. It includes advanced measurement infrastructure, distribution automation, outage-management systems, demand response, distributed energy resources and cybersecurity controls.

The electrical power relationships used in basic energy analysis are:

P = V I

where P is real power in watts (W), V is voltage in volts (V), and I is current in amperes (A). For alternating-current systems, power factor must be considered. For single-phase circuits:

P = V I cosφ

where φ is the phase angle between voltage and current, and cosφ is the power factor. These relationships apply to sinusoidal steady-state conditions; actual network studies may require separate treatment of harmonics, three-phase systems and reactive power.

Electrical energy consumed over a period is:

E = P t

where E is energy, P is average power and t is time. If power is measured in kilowatts and time in hours, energy is measured in kilowatt-hours (kWh). For variable demand, the more general relationship is:

E = ∫ P(t) dt

2.2 Smart-grid components

Important components include:

  • Advanced metering infrastructure (AMI): meters, communication networks and data-management systems that record and transmit consumption data.
  • Distribution automation: remotely controlled switches, voltage regulators and fault indicators.
  • Distributed energy resources (DERs): rooftop photovoltaics, small wind turbines, combined heat and power, batteries, electric vehicles and controllable loads.
  • Energy-management systems: software that forecasts demand, monitors assets and optimizes operation.
  • Microgrids: electrically bounded systems capable of operating with the main grid and, where designed, in an islanded mode.
  • Outage-management systems: platforms that locate faults, identify affected customers and coordinate restoration.

2.3 Distributed energy and microgrids

Distributed generation is located close to loads rather than exclusively at large central power stations. It can reduce transmission losses and improve local resilience, but it also creates operational challenges. Solar and wind generation are variable, reverse power flows may occur in distribution feeders, and protection settings may need revision.

A microgrid normally contains local generation, loads, control equipment and possibly storage. In grid-connected operation, it exchanges power with the utility. During an outage, an appropriately designed microgrid may disconnect and serve priority loads. Islanding requires careful control of voltage, frequency, protection and reconnection. It should never be assumed that a system can island safely merely because it contains batteries or solar panels.

A basic energy balance for a microgrid over an operating interval is:

Pgen + Pimport + Pdischarge = Pload + Pexport + Pcharge + Ploss

Each term represents power, normally in kW: generation, imported power, battery discharge, load, exported power, battery charging and losses. The equation is a conservation relationship. It applies at a defined boundary and time interval, provided all relevant flows are included with consistent sign conventions.

2.4 Renewable-energy integration

Renewable integration requires coordination of generation forecasts, flexible loads, storage, network capacity and market or tariff arrangements. Key strategies include:

  • locating generation where network capacity is available;
  • using batteries or other storage to shift energy from high-production to high-demand periods;
  • controlling water heating, cooling, pumping and electric-vehicle charging;
  • improving forecasting of solar irradiance, wind and demand;
  • using inverters capable of voltage and frequency support;
  • upgrading protection and distribution-management systems.

Battery round-trip efficiency is defined as:

ηrt = Eout / Ein

where Ein is energy supplied to charge the battery and Eout is energy recovered during discharge. Both quantities must be measured at the same system boundary. Auxiliary equipment and conversion losses should be included when assessing a complete storage installation.

Storage sizing must consider power capacity (kW), energy capacity (kWh), allowable depth of discharge, efficiency, degradation, response time, safety and operating conditions. A battery with high energy capacity but insufficient power capacity may not support a peak load; a high-power battery with little energy capacity may provide only brief support.

3. Demand Response and Smart Metering

3.1 Demand response

Demand response changes electricity consumption in response to prices, system conditions, direct operator signals or automated controls. It differs from energy efficiency: energy efficiency permanently reduces the energy required for a service, whereas demand response changes the timing or intensity of consumption.

Examples include:

  • pre-cooling buildings before a peak period;
  • delaying electric-vehicle charging;
  • reducing non-critical pumping or ventilation;
  • shifting industrial processes;
  • using thermal storage;
  • coordinating batteries and backup generation.

The peak reduction achieved by a program can be represented as:

ΔPpeak = Pbaseline − Pevent

where Pbaseline is the estimated demand without intervention and Pevent is demand during the response event. The baseline is not directly observable and must be estimated carefully using historical and contextual data. Weather, occupancy, production and previous control actions can affect the estimate.

A demand-response program should specify notification time, event duration, customer obligations, compensation, override conditions and performance measurement. Poorly designed programs can create rebound peaks when deferred loads operate simultaneously after an event.

3.2 Smart meters

Smart meters measure consumption at defined intervals and communicate data to utilities or authorized service providers. Depending on the design, they may also report voltage, outage conditions, power quality or tampering indicators.

Benefits include automated billing, faster outage detection, time-of-use tariffs, improved load forecasting and customer feedback. Limitations include communication failures, installation cost, data-management requirements, privacy risks and the possibility that customers cannot respond to complex tariffs.

Meter data should be governed according to purpose limitation, data minimization, retention rules, access controls and transparent customer communication. High-resolution electricity data may reveal occupancy patterns, appliance use or business activity. Thus, privacy protection is a utility-design requirement, not merely an information-technology issue.

Worked Example 1: Load shifting

An apartment building has a 120 kW evening peak. A control program shifts 25 kW of electric-vehicle charging and 15 kW of water-heating demand outside the peak period. Assuming the loads are not replaced by other simultaneous loads:

ΔPpeak = 25 + 15 = 40 kW

The new peak is:

Pnew = 120 − 40 = 80 kW

The reduction is 40 kW, or one-third of the original peak. This result describes peak demand only; it does not prove that total daily energy consumption has fallen.

4. Smart Water Systems

4.1 Water-system architecture

Urban water systems include abstraction, treatment, transmission, storage, distribution, customer use, wastewater collection, treatment and reuse. Smart water management adds flow, pressure, quality and asset-condition monitoring to these physical processes.

Typical devices include bulk flow meters, district meters, pressure sensors, acoustic leak detectors, water-quality probes, pump monitors, automated valves and customer meters. Data may be transmitted continuously or periodically, depending on the required response time and communication cost.

4.2 Water balance and non-revenue water

A simplified water balance compares water entering a defined system boundary with authorized consumption and losses:

Qin = Qauthorized + Qapparentloss + Qrealloss + Qother

where Qin is system input volume, Qauthorized is authorized consumption, Qapparentloss includes meter inaccuracies and unauthorized consumption, Qrealloss includes physical leakage and overflows, and Qother represents any separately defined category. All terms must use the same time period and volume units.

Non-revenue water is commonly associated with water supplied but not billed because of physical losses, apparent losses or authorized unbilled use. Reducing it requires a balanced program of measurement, pressure management, asset renewal, meter testing, active leakage detection and customer-account control.

4.3 Leakage detection and pressure management

Leakage may be visible, such as a surface break, or hidden within buried networks. Useful methods include:

  • comparing inlet flow with customer consumption in district-metered areas;
  • examining minimum night flow, while accounting for legitimate night use;
  • using pressure and acoustic data to identify anomalies;
  • analyzing historical bursts and pipe-condition data;
  • inspecting suspected locations with ground microphones or correlators;
  • controlling excessive pressure through pressure-reducing valves and pump management.

Pressure management must be designed carefully. Excessive pressure can increase leakage and pipe stress, but insufficient pressure can reduce service quality and create contamination risks where negative pressure occurs. Sensors should be calibrated, protected from fouling and located where measurements represent the hydraulic zone.

Water demand is often expressed as:

q = V / t

where q is average flow rate, V is volume and t is time. For a 900 m³ volume supplied over 6 hours, the average flow is 150 m³/h, or approximately 41.7 L/s because 1 m³ = 1,000 L and 1 hour = 3,600 seconds.

4.4 Water quality and predictive operation

Online sensors may monitor parameters such as turbidity, conductivity, temperature, residual disinfectant and pressure. Sensor readings are indicators, not automatic proof of regulatory compliance. They require calibration, verification, laboratory confirmation where required and documented quality-control procedures.

Predictive analytics can forecast demand, identify abnormal consumption and prioritize pipe renewal. However, algorithms trained on historical failure data may reproduce historic underinvestment in particular neighbourhoods. Engineering judgment, field inspection and community reporting must remain part of the decision process.

5. Circular Waste and Resource Systems

5.1 From disposal to circularity

A linear waste model follows the sequence extract–produce–use–dispose. A circular model seeks to retain materials and value through prevention, repair, reuse, remanufacturing, recycling, biological processing and energy recovery where appropriate. Disposal remains the least preferred option after feasible recovery pathways have been considered.

The waste hierarchy commonly prioritizes prevention, reduction, reuse, recycling and recovery before treatment and disposal. The correct ordering can vary with material, contamination, energy inputs and environmental risk; recycling is not automatically preferable if it consumes excessive resources or produces hazardous residues.

5.2 Smart waste systems

Smart waste applications include:

  • fill-level sensors in communal bins;
  • route optimization for collection vehicles;
  • weighing systems that measure material flows;
  • digital tracking of construction and demolition waste;
  • contamination detection;
  • deposit-return and incentive systems;
  • material exchanges linking one organization’s by-product to another’s input.

Collection optimization should consider more than distance. A good route accounts for vehicle capacity, service windows, traffic, crew safety, bin access, emissions and the consequences of missed collection. Sensors can reduce unnecessary trips, but devices themselves require batteries, maintenance and eventual disposal.

Construction projects have a particularly important role. Design for disassembly, standard dimensions, material passports, take-back agreements, prefabrication and accurate quantity control can reduce waste before it reaches the collection system. Waste-management plans should identify material streams, storage arrangements, contractors, documentation and recovery targets.

5.3 Circularity indicators

A simple recovery rate may be expressed as:

R = Mrecovered / Mgenerated × 100%

where Mgenerated is the mass of waste generated and Mrecovered is the mass directed to a defined recovery process. The boundary must be stated: recovery may mean collection for recycling, successful reprocessing or final substitution of virgin material. Mass recovery alone does not measure toxicity, quality loss, transport impacts or actual market demand.

6. Coordinated Utility Management

Electricity, water and waste systems are physically and operationally linked. Water utilities consume substantial electricity for pumping and treatment. Electricity generation may require water. Wastewater treatment produces biogas, and organic waste can support energy recovery. Construction activities affect all systems through material use, excavation, demand peaks and infrastructure disruption.

A coordinated utility-management platform may include:

  1. a common geographic information system showing assets and service zones;
  2. standardized asset identifiers and data models;
  3. a time-series database for sensor readings;
  4. dashboards for operators and managers;
  5. event management and work-order integration;
  6. analytics for forecasting, anomaly detection and maintenance;
  7. role-based access and audit logs;
  8. interfaces with billing, emergency management and customer channels.

Interoperability is essential. Proprietary systems that cannot exchange data create duplicated surveys, delayed response and vendor dependence. Open standards and documented application programming interfaces can improve integration, but they do not eliminate the need for data governance and testing.

Digital twins

A digital twin is a continuously updated digital representation of a physical asset or system, linked through data and models. A useful utility digital twin may combine pipe geometry, pump curves, sensor data, maintenance history, hydraulic or electrical models and operational status. A three-dimensional model alone is not necessarily a digital twin.

The quality of a twin depends on data accuracy, update frequency, model assumptions and validation. Operators should know whether a displayed condition is measured, estimated or simulated. False precision can be dangerous during emergencies.

Multi-utility optimization

Integrated optimization may seek to minimize cost, emissions, water losses, waste transport or outage risk subject to engineering and regulatory constraints. In practice, objectives can conflict. For example, reducing pumping during a low-price electricity period may conflict with maintaining reservoir levels, fire-flow capacity or water-quality requirements. The solution must therefore include constraints, priorities and human approval procedures rather than relying on a single opaque score.

7. Illustrative Integrated Case: Riverside District

Background

Riverside is an illustrative mixed-use district of 8,000 residents, offices, schools and a small health facility. Its electrical demand is highest between 17:00 and 21:00. The water network experiences unexplained night flows, and waste vehicles make partially empty collection trips.

Problem

The district faces three linked concerns: rising electricity peak charges, uncertain water losses and avoidable collection mileage. Existing meters are read manually, utility data are held by separate departments, and the health facility requires reliable backup power.

Analysis

The project team first established a common asset map and installed district electricity and water meters. Building-level electricity data were collected at suitable intervals with privacy controls. Water pressure sensors were installed at network inlets and critical elevation points. Waste bins serving commercial areas received fill-level sensors, while vehicle routes and service constraints were documented.

The energy assessment identified 40 kW of flexible electric-vehicle and hot-water demand. A rooftop photovoltaic system and battery were evaluated against roof structure, fire safety, interconnection requirements, lifecycle cost and the health facility’s critical-load profile. The water assessment compared night flow with authorized night consumption and inspected high-risk pipe segments. The waste assessment compared sensor-informed routes with fixed schedules.

Approach and solution

The district implemented a staged program:

  • demand-response controls shifted selected loads away from the evening peak;
  • photovoltaic generation served daytime loads, while the battery supported critical loads and selected peak periods;
  • a microgrid controller was installed for defined priority circuits, with tested islanding and reconnection procedures;
  • water data were divided into hydraulic zones, and pressure was reduced where service levels permitted;
  • acoustic surveys targeted zones with persistent unexplained night flow;
  • commercial waste collection was scheduled using fill thresholds, vehicle capacity and time windows;
  • a common dashboard displayed alerts but did not replace engineering approval.

Outcome

The project reduced the district’s observed peak demand and identified a leaking main that had not produced a visible surface failure. Collection mileage fell because low-fill visits were avoided. The health facility gained a documented backup-power procedure rather than an assumed capability.

The project also revealed limitations. Some sensors failed during communications outages, residents raised concerns about detailed energy data, and the first waste-routing algorithm produced routes that were efficient in distance but unsafe for reversing near a school. These problems were corrected through offline data buffering, privacy rules, manual review and revised safety constraints.

Learning points

The case demonstrates that integration is organizational as well as technical. Sensors, models and dashboards create value only when responsibilities, maintenance, cybersecurity, safety and public communication are designed alongside the equipment. Pilot projects should be evaluated against a baseline and expanded only after data quality and operational procedures have been demonstrated.

8. Implementation, Governance and Risk

8.1 Planning and procurement

A utility digitization project should begin with service outcomes rather than technology selection. Procurement documents should specify data ownership, interoperability, cybersecurity, maintenance, calibration, training, warranties, software updates, accessibility and exit arrangements if a supplier changes.

Lifecycle cost includes capital expenditure, communications, licenses, electricity, calibration, replacement, cybersecurity, data storage, staff and decommissioning. A low-cost sensor with frequent failure may be more expensive than a robust device over its service life.

8.2 Cybersecurity and resilience

Connected utilities are critical infrastructure. Threats include unauthorized access, ransomware, manipulated sensor readings, denial of service and unsafe control commands. Basic controls include network segmentation, strong authentication, least-privilege access, encryption where appropriate, secure configuration, patch management, backups, incident response and recovery exercises.

Cybersecurity must be balanced with operational continuity. A water plant should be able to maintain safe operation if its external communications fail. Manual fallback procedures, local control and tested emergency modes are essential.

8.3 Equity and public accountability

Smart tariffs and digital services may disadvantage households without reliable internet access, flexible work schedules, modern appliances or the ability to invest in efficiency. Programs should offer accessible communication, protections for vulnerable customers and transparent appeal mechanisms. Energy and water disconnection policies require special care because these services support health and safety.

Automation also raises accountability questions. If an algorithm prioritizes one pipe replacement over another, the utility must be able to explain the relevant data, criteria and review process. AI can support forecasting, image interpretation and anomaly detection, but it should not conceal responsibility for safety-critical decisions.

9. Best-Practice Checklist

A professionally managed smart-utility project should:

  • define measurable service and sustainability outcomes;
  • establish a reliable baseline before claiming improvement;
  • use calibrated sensors and documented data-quality procedures;
  • design communications for the required latency and availability;
  • integrate cybersecurity from the beginning;
  • preserve manual and local fallback operation;
  • assess lifecycle cost rather than purchase price alone;
  • protect privacy and explain data use to customers;
  • test algorithms for bias, safety and unusual conditions;
  • involve operators, maintenance staff and affected communities;
  • validate pilots before district-wide deployment;
  • review environmental impacts of devices, batteries and data infrastructure.

Chapter Summary

Smart utility systems combine physical infrastructure, sensing, communications, analytics, control and governance. Smart grids enable two-way power flows, distributed energy, renewable integration, storage and demand response. Smart meters improve visibility and support new tariffs, but they create privacy, cybersecurity and data-management responsibilities. Water intelligence depends on accurate flow and pressure measurement, water balances, leakage detection, pressure control and asset management. Circular waste systems seek to prevent waste and retain material value through reuse, repair, recycling, biological processing and carefully assessed recovery. Integrated utility platforms and digital twins can coordinate electricity, water and waste operations, but their reliability depends on data quality, interoperability, human oversight and resilient fallback procedures. Effective smart-city construction and management therefore require both technical competence and responsible institutional design.

Key Terms

Advanced metering infrastructure: Integrated meters, communications and data systems for automated measurement and transmission.

Demand response: Planned change in electricity consumption in response to prices, signals or system conditions.

Distributed energy resource: Small-scale generation, storage or controllable load connected near users.

Digital twin: A data-linked digital representation of a physical asset or system.

Microgrid: A bounded electrical system containing loads and resources that can operate with a main grid and, if designed, independently.

Non-revenue water: Water supplied to a system that is not billed because of physical loss, apparent loss or authorized unbilled use.

Pressure management: Regulation of water pressure to maintain service while reducing leakage and pipe stress.

Smart grid: An electricity network enhanced by two-way communication, measurement and automated control.

Smart meter: A meter capable of recording and communicating utility-use data.

Distributed generation: Electricity generation located close to consumption rather than solely at central stations.

Energy storage: Equipment that stores energy for later use, such as batteries or thermal storage.

Power factor: The ratio of real power to apparent power in an AC system, commonly represented by cosφ.

Water balance: Accounting of water entering, being consumed and being lost within a defined boundary.

Circular economy: An economic model that retains products and materials in use and minimizes waste.

Material recovery: Retrieval of useful materials or energy from a waste stream.

Interoperability: The ability of systems and organizations to exchange and use information effectively.

Advanced analytics: Computational methods used to identify patterns, forecast conditions or support decisions.

Cybersecurity: Protection of digital systems, data and control functions from unauthorized or harmful activity.

Utility digital platform: An integrated information environment for monitoring and managing utility assets and services.

Review Questions

Short Answer Questions

  1. What distinguishes a smart grid from a conventional electricity grid?
  2. Define distributed energy resource and give two examples.
  3. Why is demand response different from energy efficiency?
  4. What are physical and apparent water losses?
  5. State two principles of circular waste management.

Long Answer Questions

  1. Explain the architecture, benefits and operational challenges of a smart electricity grid.
  2. Discuss how renewable generation, batteries and demand response can be coordinated in a microgrid.
  3. Explain how smart metering can improve utility management while creating privacy and cybersecurity risks.
  4. Describe a systematic approach to water-leakage detection and pressure management.
  5. Evaluate the role of interoperability and digital twins in coordinated utility management.

Analytical / Application Questions

  1. A building has a 180 kW peak. Controls shift 35 kW of vehicle charging and 20 kW of water heating outside the peak period. Calculate the new peak, assuming no rebound or replacement load.
  2. A district water meter records 12,000 m³ entering during a month. Authorized consumption is 9,100 m³, apparent losses are estimated at 500 m³ and other authorized unbilled use is 600 m³. Calculate the remaining volume attributable to real loss using the stated water-balance categories.
  3. Design a preliminary integrated utility strategy for a new university campus. Identify the energy, water, waste, data-governance and resilience measures you would prioritize, and explain the trade-offs involved.

Multiple Choice Questions with Answers

Question 1

Which feature most clearly distinguishes a smart grid from a conventional one-way electricity grid?

A. Use of only large fossil-fuel power stations

B. Two-way communication and coordinated control of resources

C. Elimination of all electricity storage

D. Removal of distribution networks

Correct Answer: B. Two-way communication and coordinated control of resources

Question 2

A microgrid energy balance must account for generation, imports, load, storage and which additional item?

A. Only building height

B. Power losses and exports

C. Road traffic volume

D. Waste composition only

Correct Answer: B. Power losses and exports

Question 3

Demand response primarily changes:

A. The timing or intensity of electricity consumption

B. The chemical composition of drinking water

C. The legal ownership of a building

D. The physical density of construction materials

Correct Answer: A. The timing or intensity of electricity consumption

Question 4

A battery receives 100 kWh during charging and delivers 85 kWh during discharge. Its round-trip efficiency is:

A. 15%

B. 85%

C. 100%

D. 185%

Correct Answer: B. 85%

Question 5

Which measurement is especially useful for identifying hidden water leakage in a district?

A. Minimum night flow, interpreted with legitimate night use

B. Annual rainfall alone

C. Building façade color

D. Number of streetlights

Correct Answer: A. Minimum night flow, interpreted with legitimate night use

Question 6

In a water balance, apparent losses commonly include:

A. Pipe bursts only

B. Evaporation from reservoirs only

C. Meter inaccuracies and unauthorized consumption

D. Electricity used by pumps

Correct Answer: C. Meter inaccuracies and unauthorized consumption

Question 7

Which option is generally highest in the waste hierarchy?

A. Prevention and reduction

B. Landfilling

C. Uncontrolled disposal

D. Disposal without sorting

Correct Answer: A. Prevention and reduction

Question 8

Why is interoperability important in coordinated utility management?

A. It prevents all equipment maintenance

B. It allows different systems to exchange and use information

C. It removes the need for cybersecurity

D. It guarantees that every sensor is accurate

Correct Answer: B. It allows different systems to exchange and use information

Question 9

A building peak is 180 kW. If 35 kW and 20 kW of loads are shifted away, the new peak is:

A. 125 kW

B. 145 kW

C. 165 kW

D. 235 kW

Correct Answer: B. 145 kW

Question 10

Which is an appropriate cybersecurity practice for connected utility systems?

A. Using one shared administrator password

B. Removing all local fallback controls

C. Applying least-privilege access and network segmentation

D. Publishing detailed customer meter data openly

Correct Answer: C. Applying least-privilege access and network segmentation

Smart Cities
Chapter 10 of 15