12. Distribution-System Protection and AutomationIntroduction and ContextDistribution systems occupy the final and most diverse part of the electric power network. They connect substations to industrial consumers, commercial premises, public infrastructure, and residential customers. Unlike transmission systems, distribution networks commonly contain numerous laterals, relatively short lines, unbalanced loading, overhead and underground sections, distributed generation, and protection devices installed at many locations. These characteristics make distribution protection a coordination problem rather than simply a relay-setting problem. The central objective is selective isolation of faults: the smallest practical section should be disconnected, healthy customers should remain supplied, equipment should be protected from thermal and mechanical damage, and restoration should occur rapidly. At the same time, protection must remain dependable for faults within its zone and secure against maloperation caused by load current, inrush, harmonics, switching events, and changing network configuration. Traditional distribution protection was designed for predominantly radial, unidirectional power flow. The growth of photovoltaic generation, battery storage, electric vehicles, active demand, and microgrids has challenged this assumption. Modern distribution protection therefore combines overcurrent devices with communications, automation, fault indicators, distributed intelligence, and increasingly adaptive algorithms. Learning ObjectivesAfter studying this chapter, the reader should be able to: 1. Explain the protection functions of distribution feeders, reclosers, sectionalizers, fuses, and feeder relays. 2. Coordinate overcurrent devices for phase and earth faults while considering equipment ratings and customer requirements. 3. Select grounding arrangements and design suitable earth-fault protection. 4. Analyze the effects of distributed energy resources and bidirectional power flow on conventional protection. 5. Describe feeder automation, self-healing networks, adaptive protection, and microgrid protection. 6. Evaluate technical, operational, cybersecurity, regulatory, and resilience considerations in distribution protection. 7. Develop and defend a protection and automation strategy for a practical feeder. The Distribution Protection ProblemA distribution feeder normally contains a substation circuit breaker or relay, one or more pole-mounted or pad-mounted reclosers, sectionalizers, fuses, switches, and customer protection. The devices must operate in a coordinated sequence. For a fault on a fused lateral, the lateral fuse should normally clear the fault without interrupting the entire feeder. For a temporary fault on the main feeder, a recloser may trip, wait, and reclose. If the fault persists, the recloser locks out and isolates the feeder section. Protection performance is commonly evaluated using four related requirements. Reliability includes dependability, meaning operation when required, and security, meaning restraint when operation is not required. Selectivity requires the nearest suitable device to clear the fault. Speed limits equipment damage and improves voltage stability. Sensitivity ensures that even low-current faults, particularly high-resistance earth faults, are detected. These requirements are not independent: increasing sensitivity may reduce security, while very fast operation may reduce coordination margin. Distribution protection is also constrained by system topology. In a radial feeder, current generally flows from the substation toward the load, so time-current coordination is relatively straightforward. In a looped or actively operated feeder, fault current may arrive from more than one direction. Directional elements, communications, and topology-aware settings may then be necessary. Important Devices and Their Functional RolesFeeder Circuit Breakers and RelaysThe substation feeder breaker provides the primary interrupting device for the feeder. Its associated relay may include phase overcurrent, earth-fault overcurrent, negative-sequence, undervoltage, breaker-failure, and communications-assisted functions. The breaker must interrupt the maximum prospective fault current at its installation point and must also operate for faults not cleared by downstream devices. The feeder relay is usually coordinated with downstream reclosers and fuses. Its time-current characteristic is selected so that a downstream device operates first for faults within its zone, while the feeder breaker provides backup after a coordination interval. This interval must include relay operating time, breaker opening time, overtravel, current-transformer errors, and a safety margin. ReclosersA recloser is an automatic switching device capable of detecting fault current, opening the circuit, waiting for a programmed dead time, and reclosing. Many distribution faults are transient—for example, those caused by branches, animals, lightning flashover, or temporary contact with vegetation. Reclosing restores service without a permanent outage. A recloser may be programmed with fast and delayed shots. A fast shot can clear a temporary fault before a downstream fuse melts, thereby preventing an unnecessary fuse operation. Delayed shots allow fuse operation for permanent lateral faults. This arrangement is called fuse-saving coordination. Alternatively, fuse-blowing coordination allows the fuse to clear both temporary and permanent faults, reducing the number of recloser operations but increasing momentary interruptions for customers downstream of the fuse. Recloser settings include phase pickup, earth-fault pickup, time-current curves, number of shots, sequence intervals, reset time, lockout logic, and minimum operating current. Modern electronic reclosers may also support directional protection, voltage supervision, synchrocheck, communications, fault recording, and remote control. SectionalizersA sectionalizer does not normally interrupt fault current. It counts upstream recloser operations while sensing current and opens during a dead interval after the upstream device has interrupted the fault. It therefore isolates a faulted section without requiring its own high interrupting capability. A sectionalizer is useful where a lateral or feeder segment should be separated after repeated fault operations. Coordination requires correct counting logic and timing. If the sectionalizer opens too early, it may interrupt healthy load or fail to coordinate with the recloser. If it counts incorrectly because of load transfers or communications errors, the intended isolation sequence may fail. Sectionalizers are increasingly implemented as remotely controlled switches with fault-passage indicators rather than as purely electromechanical counters. FusesFuses are economical, simple, and inherently fast. Their principal limitations are single-use operation, tolerance in melting characteristics, limited adjustability, and difficulty coordinating with changing fault levels. Fuse coordination requires distinguishing between the minimum-melting curve and the total-clearing curve. A downstream fuse should melt before the upstream fuse begins to melt, with an appropriate margin for manufacturing tolerances and transient effects. Fuse saving can reduce permanent outages but may produce repeated voltage interruptions and stress customer equipment. Fuse-blowing schemes provide clearer lateral discrimination but may result in more truck rolls. The appropriate choice depends on customer sensitivity, feeder construction, fault history, and utility operating policy. Fault Indicators and Intelligent SwitchesFault indicators detect fault passage using current magnitude, rate of change, voltage loss, or directional quantities. Their visual or communicated indication helps crews locate faults. Intelligent electronic devices can combine sensing, switching, communications, and automation in one field unit. Such devices form the physical foundation of modern distribution management systems. Coordination of Distribution ProtectionProtection coordination begins with a system model. The engineer gathers conductor impedances, transformer data, grounding details, load currents, motor contributions, distributed-generation contributions, equipment ratings, and feeder topology. Short-circuit calculations should consider both maximum and minimum fault current. Maximum current determines interrupting duty and instantaneous settings; minimum current determines sensitivity and backup operation. Time-Current CoordinationFor radial feeders, coordination is commonly represented on log-log time-current characteristic plots. Curves for the feeder relay, recloser, fuse, transformer damage limit, conductor thermal limit, and customer protection are superimposed. The objective is to maintain separation between primary and backup devices across the relevant current range. A downstream device should operate first for a fault in its zone. The upstream device must remain closed long enough to allow the primary device to clear the fault. For a relay-recloser pair, the coordination interval is often specified as a grading margin rather than a universal value. It depends on relay and breaker technology, current-transformer performance, curve tolerances, and whether instantaneous functions are used. The operating time of an inverse-time overcurrent relay can be represented generally as t = TMS × K / [(I/Ip)^α − 1] + t_c, where TMS is the time multiplier setting, Ip is pickup current, I is measured current, and K, α, and tc depend on the selected characteristic and relay model. The equation is useful for understanding trends: higher fault current produces faster operation, while increasing TMS delays operation. Actual engineering must use the manufacturer’s characteristic and applicable standards. Phase and Earth-Fault SettingsPhase pickup must exceed maximum expected load current, including permissible overload, cold-load pickup, motor starting, and transformer energization effects. It must nevertheless be low enough to detect the minimum phase fault. Earth-fault pickup can often be set below phase pickup because normal residual current is smaller, but unbalance, cable charging, CT errors, and feeder capacitance impose a lower practical limit. For a residual connection, the earth-fault element responds to the vector sum of phase currents. A core-balance CT can provide greater sensitivity because all phase conductors pass through one magnetic core and normal load current cancels. In compensated or isolated systems, earth-fault current may be small and predominantly capacitive; wattmetric, directional, or sensitive transient-based methods may then be preferable to simple magnitude-based overcurrent protection. Coordination with FusesA recloser and fuse must be coordinated for the selected operating philosophy. In a fuse-saving scheme, the recloser’s fast curve must lie below the fuse minimum-melting curve for the expected fault-current range. Its delayed curve must lie above the fuse total-clearing curve, allowing the fuse to clear a permanent fault before the recloser trips on a delayed operation. In fuse-blowing coordination, the recloser curve is intentionally delayed relative to the fuse. Coordination should be checked for faults at several locations, not only at the end of the feeder. Fault-current variation due to line impedance, transformer connections, generation output, and grounding can cause coordination at one location to fail at another. Grounding and Earth-Fault ProtectionGrounding has two complementary purposes: controlling system voltage relative to earth and providing a path for fault current. Equipment grounding protects people and property by bonding exposed conductive parts and allowing protective devices to operate. System grounding establishes the electrical relationship between the source neutral and earth. Common system-grounding arrangements include solid grounding, resistance grounding, reactance grounding, and resonant or compensated grounding. Solid grounding produces relatively high earth-fault current and facilitates rapid operation, but it can increase equipment damage and touch-voltage hazards. Resistance grounding limits current and reduces damage, but protection must be sensitive enough to detect the restricted fault current. Ungrounded and resonant systems may continue operating during a first earth fault, but transient overvoltages and fault-location difficulties require careful engineering. The design process should consider: - permissible touch and step voltages;
- soil resistivity and seasonal variation;
- ground-grid geometry and conductor thermal duty;
- neutral displacement and temporary overvoltage;
- fault-current magnitude and duration;
- parallel metallic paths, cable screens, and utility neutrals;
- operation of earth-fault relays and residual-current devices.
A low measured earth resistance alone does not guarantee safety. The distribution of potential across the site, bonding integrity, fault-clearing time, and accessible locations are equally important. Grounding studies should therefore combine fault calculations with a grounding-grid and personnel-safety assessment. Distributed Energy Resources and Bidirectional Fault CurrentPhotovoltaic inverters and battery energy-storage systems change distribution protection in several ways. They can contribute fault current, although inverter current is usually controlled and limited rather than governed by the natural subtransient response of a synchronous generator. They can also alter the magnitude and direction of load current, raise minimum voltage, cause reverse power flow, and create operating conditions for which conventional relay settings were not designed. A downstream fault may be supplied by both the substation and a local generator. The feeder relay may see reduced current from the substation because the local source supplies part of the fault. Conversely, an upstream fault may receive current from the distributed resource and cause an incorrectly coordinated device to trip. Directional overcurrent, negative-sequence protection, transfer trip, voltage-based supervision, and intentional DER disconnection are possible solutions. Protection engineers must distinguish between grid-connected and islanded operation. A microgrid may require one set of settings while connected to the utility and another while operating independently. Transition logic must prevent unsafe reclosing onto an energized island. Synchronism checking, anti-islanding controls, communications, and clearly defined operating boundaries are essential. Feeder Automation and Self-Healing NetworksFeeder automation applies sensing, communications, control logic, and remotely operated switching to reduce outage duration and improve visibility. A typical fault-location, isolation, and service-restoration sequence is: 1. Detect abnormal current, voltage, or protection operation. 2. Determine the likely faulted section using relay records, fault indicators, and topology data. 3. Open switches that isolate the suspected section. 4. Verify that the isolated section is de-energized and that switching will not violate safety or equipment constraints. 5. Close a normally open tie or alternate supply path. 6. Restore healthy sections while maintaining voltage, thermal, and protection limits. This process is often called FLISR. It may be centrally controlled by a distribution management system or executed through distributed intelligence in field devices. Automation does not eliminate the need for protection coordination. Rather, it adds a supervisory layer that must be secure against incorrect topology, stale measurements, failed communications, and erroneous switching commands. A self-healing network is not necessarily a fully meshed network. Many practical systems retain radial operation after restoration because radial topology simplifies fault protection and reduces circulating current. Automation selects among permissible radial configurations. The quality of the network model is therefore critical: an incorrect switch status or connectivity model can cause an unsafe restoration sequence. Adaptive Protection and Microgrid OperationAdaptive protection changes relay settings or protection logic according to the active network condition. Relevant conditions include feeder configuration, DER status, islanding, maintenance outages, seasonal loading, and switching states. An adaptive scheme may select from pre-engineered setting groups or calculate settings using a validated control center algorithm. Adaptive protection should not be treated as unrestricted real-time optimization. Each setting group must be tested for sensitivity, selectivity, security, and communications failure. A fallback group should be available when communications are lost. Cybersecurity controls must protect setting changes from unauthorized access, and every change should be logged for operational accountability. Microgrid protection presents a particularly demanding case. In grid-connected mode, fault current may be comparatively high because the utility supports the fault. In islanded mode, inverter-based sources may provide limited current, making conventional overcurrent protection insensitive. Voltage, frequency, differential, negative-sequence, directional, and communications-assisted methods may be combined. Load shedding and controlled disconnection of noncritical sections may be required to preserve a stable island. Detailed Applied Case: Automated Urban Feeder with Solar GenerationBackgroundConsider an illustrative 11-kV urban feeder supplied from a substation through a feeder breaker. The feeder serves residential loads, a hospital, commercial customers, and several lateral sections. Two reclosers divide the main feeder, while fused laterals supply smaller neighborhoods. A normally open tie connects the feeder to an adjacent feeder. Rooftop photovoltaic systems and a community battery are connected downstream of the second recloser. Situation and ProblemThe utility has experienced three difficulties. First, a tree-contact fault on a fused lateral caused the upstream recloser to lock out because the fuse and recloser were poorly coordinated at low fault current. Second, reverse power flow occurred during light-load, high-solar conditions. Third, the hospital experienced unnecessarily long interruptions because field crews had to patrol the feeder before transferring healthy sections. AnalysisThe protection study identified a wide range of fault currents. Solar inverters contributed limited current and did not always provide sufficient magnitude for the existing phase overcurrent elements. During some configurations, local generation reduced the fault current measured by the substation relay. The existing scheme also lacked directional supervision, reliable fault indicators, and a validated switching model. The grounding study showed that the solidly grounded system provided adequate earth-fault current, but the earth-fault element on the second recloser was set too high to detect high-resistance faults near the end of a lateral. The hospital supply required a restoration sequence that preserved selectivity and prevented reclosing onto an energized island. Protection and Automation StrategyThe utility adopted the following strategy. Recloser curves were revised using minimum and maximum fault-current cases, and fuse coordination was checked along the complete lateral length. A sensitive earth-fault element using a core-balance CT was installed on selected laterals. Directional elements were enabled at the feeder breaker and second recloser, with blocking logic for known reverse-flow conditions. Fault indicators were installed at strategic lateral points and integrated with the distribution management system. The normally open tie was motorized, and a FLISR sequence was developed. The sequence could isolate the faulted section, verify dead-line conditions, and transfer healthy load subject to thermal and voltage limits. The hospital section received priority restoration, but the automation system could not transfer it unless synchronism and protection conditions were satisfied. Two setting groups were created: grid-connected operation and an approved microgrid mode for the hospital and battery-supported section. Communications failure caused automatic reversion to the conservative group, while all setting changes required authorization and event logging. OutcomeThe revised arrangement improved discrimination between lateral and main-feeder faults, reduced unnecessary feeder-wide interruptions, and shortened restoration time for healthy sections. The study also showed that automation alone could not solve the problem: accurate models, appropriate grounding, directional logic, field commissioning, and operating procedures were all necessary. Learning PointsThe case demonstrates five principles. Protection must be studied over the full range of operating conditions. Distributed generation changes both fault magnitude and direction. Automation requires validated topology and safety checks. Sensitive earth-fault protection is valuable where high-resistance faults are credible. Finally, resilience depends on coordinated technical and organizational measures rather than on a single intelligent device. Challenges, Risks, and Common MistakesA frequent mistake is coordinating devices only for maximum short-circuit current. Minimum fault current may govern sensitivity and may expose a failure to trip. Another mistake is ignoring cold-load pickup after an outage; restoration can produce currents far above normal demand and cause inappropriate tripping. Transformer inrush, motor starting, capacitor switching, and harmonic distortion must also be considered. Other common problems include treating a recloser as a substitute for a complete protection study, using a fuse curve without accounting for tolerance, assuming that inverter-based resources behave like synchronous generators, and failing to coordinate protection after a feeder reconfiguration. Incorrect CT polarity, saturated CTs, stale communications, and untested automation sequences can produce severe consequences. Automation introduces additional risks. A communications network may be unavailable during storms precisely when automation is most needed. A cyberattack could alter settings or issue unauthorized switching commands. Excessive dependence on remote control may weaken local operating competence. Consequently, systems should be designed with fail-safe states, local backup protection, role-based access, time-synchronized event records, network segmentation, and periodic testing. Professional, Regulatory, and Ethical ConsiderationsDistribution protection affects public safety, continuity of essential services, equipment damage, and emergency response. Engineers must comply with applicable grid codes, electrical safety rules, grounding standards, protection and control standards, cybersecurity requirements, and utility operating procedures. Exact requirements vary by jurisdiction, but the principles of documented design, independent review, commissioning, maintenance, and change management are broadly applicable. Ethical practice requires transparent treatment of uncertainty. If a protection scheme depends on communications availability, a particular DER operating mode, or an assumed fault level, those assumptions must be recorded and communicated to operators. The protection engineer must not conceal limitations merely because a nominal study case appears satisfactory. Critical loads should be identified through a structured risk process rather than informal preference. Emerging Developments and Best PracticesDistribution protection is moving toward greater use of synchronized measurements, digital substations, high-speed communications, and model-based operational platforms. Inverter controls are becoming more capable of providing fault-current support, grid-forming behavior, voltage support, and controlled islanding. Machine-learning methods may assist fault classification and asset diagnostics, but they should supplement—not replace—validated protection logic, because explainability, rare-event behavior, and cybersecurity remain concerns. Best practice includes the following: - maintain an accurate, version-controlled network model;
- calculate maximum and minimum faults for all credible configurations;
- coordinate phase and earth-fault devices using manufacturer data;
- verify grounding, touch voltage, and bonding performance;
- include DER and microgrid operating modes in protection studies;
- test recloser, sectionalizer, fuse, relay, and communications interactions;
- design automation with safe fallback and manual operating procedures;
- record settings, assumptions, test results, and changes;
- perform periodic disturbance-record and misoperation analysis;
- integrate cybersecurity and physical security into protection design.
Chapter SummaryDistribution-system protection is a coordinated arrangement of relays, breakers, reclosers, sectionalizers, fuses, grounding systems, sensors, communications, and operating procedures. Its purpose is to isolate faults selectively, quickly, and safely while maintaining supply to healthy customers. Radial systems can often be coordinated with time-current characteristics, but distributed generation and changing topology require directional, adaptive, and communications-assisted methods. Grounding determines fault-current behavior, personnel safety, equipment stress, and earth-fault sensitivity. Reclosers improve continuity for temporary faults, sectionalizers isolate sections during upstream dead time, and fuses provide economical lateral protection. Feeder automation and FLISR reduce restoration time, but their success depends on accurate topology, secure communications, validated logic, and operator oversight. Microgrids and inverter-based resources require separate consideration of grid-connected and islanded modes. A resilient protection system is therefore not merely a collection of devices; it is an engineered, tested, governed, and continuously maintained operational system. Key TermsAdaptive protection: Protection that changes settings or logic according to network configuration or operating condition. Cold-load pickup: The temporary increase in feeder current when supply is restored after an outage. Coordination margin: Time or current separation maintained between primary and backup protection devices. Dependability: The ability of protection to operate when it is required to do so. Directional overcurrent protection: Overcurrent protection that responds only when current flows in a specified direction. Earth-fault protection: Protection designed to detect current resulting from a conductor-to-earth fault. FLISR: Fault location, isolation, and service restoration using automated sensing and switching. Fuse-saving coordination: A scheme in which a recloser fast operation attempts to clear temporary faults before a fuse melts. Grading: The process of establishing coordinated operating relationships among protection devices. Grounding: Establishing conductive connections between electrical systems, equipment, and earth for safety and operational control. High-resistance fault: A fault involving significant impedance, producing relatively low fault current. Microgrid: A bounded electrical network capable of operating connected to a utility and, under defined conditions, independently. Recloser: An automatic circuit-interrupting device that opens and recloses according to a programmed sequence. Sectionalizer: A device that isolates a feeder section during an interruption produced by an upstream protective device. Security: The ability of protection to avoid unwanted operation. Selectivity: The property by which only the faulted section is disconnected where practical. Self-healing network: A distribution network that detects faults and automatically isolates and restores service to healthy sections. Touch voltage: The voltage difference between an accessible grounded object and a person’s feet during a fault. Time-current characteristic: The relationship between fault current magnitude and protective-device operating time. Transfer trip: A communications-assisted protection signal that causes a remote device to trip. Review QuestionsShort Answer Questions1. Distinguish dependability from security in distribution protection. 2. What is the principal operating difference between a recloser and a sectionalizer? 3. Why must both maximum and minimum fault currents be calculated? 4. State two reasons why distributed generation complicates feeder protection. 5. What is the purpose of a core-balance current transformer in earth-fault protection? Long Answer Questions1. Explain the coordination process among a feeder relay, recloser, sectionalizer, and fused lateral. 2. Compare fuse-saving and fuse-blowing coordination, including their effects on customers and utility operations. 3. Discuss how grounding choice influences earth-fault current, equipment stress, protection sensitivity, and personnel safety. 4. Describe the architecture and operating sequence of a FLISR scheme. 5. Explain the protection requirements of a microgrid in grid-connected and islanded modes. Analytical / Application Questions1. A photovoltaic-rich feeder experiences reverse power flow during midday and reduced fault current at the substation relay. Propose protection functions and setting-group changes that could maintain selectivity. 2. A recloser repeatedly locks out for faults on a fused lateral, although the lateral fuse is correctly rated for load current. Identify likely coordination and study errors and propose a systematic investigation. 3. Design a restoration strategy for a feeder supplying a hospital, residential load, and battery storage through a normally open tie. Specify the measurements, interlocks, protection checks, and fallback actions required before restoration. 22. Multiple Choice Questions with AnswersQuestion 1Which device normally isolates a feeder section during the dead time created by an upstream recloser, without being required to interrupt the original fault current? A. Sectionalizer B. Feeder circuit breaker C. Current transformer D. Surge arrester Correct Answer: A. Sectionalizer Question 2In a fuse-saving scheme, the recloser fast curve is generally coordinated so that it operates before the fuse’s: A. Total-clearing curve B. Minimum-melting curve C. Voltage rating D. Interrupting-current rating Correct Answer: B. Minimum-melting curve Question 3Why are minimum fault-current calculations essential in distribution protection studies? A. They determine transformer efficiency B. They establish the maximum breaker interrupting duty C. They test whether protection remains sensitive to low-current faults D. They determine customer power factor Correct Answer: C. They test whether protection remains sensitive to low-current faults Question 4Which condition most directly indicates a need for directional overcurrent protection on an actively operated feeder? A. Constant radial power flow only B. Possible fault current from more than one direction C. Low customer load diversity D. Use of underground cables only Correct Answer: B. Possible fault current from more than one direction Question 5A core-balance current transformer improves earth-fault detection primarily because it: A. Raises system voltage during faults B. Measures the magnetic sum of conductors with normal-load cancellation C. Eliminates the need for grounding D. Prevents all CT saturation Correct Answer: B. Measures the magnetic sum of conductors with normal-load cancellation Question 6Which sequence best represents a basic FLISR operation? A. Restore first, calculate later, then isolate the fault B. Detect, isolate, verify, and restore healthy sections C. Open every feeder breaker and wait for manual repair D. Change relay settings before identifying the faulted section Correct Answer: B. Detect, isolate, verify, and restore healthy sections Question 7Why can inverter-based distributed generation make conventional overcurrent protection insensitive? A. Inverters always produce unlimited fault current B. Inverters may limit and control their fault-current contribution C. Inverters eliminate all voltage disturbances D. Inverters prevent earth faults from occurring Correct Answer: B. Inverters may limit and control their fault-current contribution Question 8Which statement about grounding is most accurate? A. A low earth resistance alone guarantees personnel safety B. Grounding affects fault current, voltage rise, protection operation, and personnel safety C. Grounding is required only for underground feeders D. Grounding has no effect on earth-fault relay sensitivity Correct Answer: B. Grounding affects fault current, voltage rise, protection operation, and personnel safety Question 9What is a necessary feature of a dependable adaptive-protection scheme? A. Unlogged setting changes made by any user B. A validated fallback condition when communications fail C. Permanent dependence on one communication channel D. Removal of local protection functions Correct Answer: B. A validated fallback condition when communications fail Question 10In a microgrid operating in islanded mode, overcurrent protection may become inadequate mainly because: A. Fault current can be limited by inverter-based sources B. The network has no loads C. Grounding becomes irrelevant D. Voltage and frequency cannot be measured Correct Answer: A. Fault current can be limited by inverter-based sources
|