Fire Suppression Systems

Chapter 4
Water Supplies, Fire Pumps and Hydraulics

Diploma in fire and Safety
Fire Suppression Systems   •   Diploma

Water Supplies, Fire Pumps and Hydraulics

Introduction and Context

A fire-suppression system is only as effective as its water supply. Sprinklers, hydrants, hose reels and fixed water-spray systems require water at a specified flow rate and pressure for the required duration. A system may contain excellent detection and discharge equipment, yet fail if the tank is empty, the pump cannot start, a valve is closed, or the distribution main cannot deliver the design demand.

Water-supply engineering therefore connects fire risk assessment with practical hydraulic performance. The fire-safety professional must be able to identify water sources, understand storage and pumping arrangements, interpret pressure and flow measurements, estimate friction and elevation losses, and judge whether a supply is reliable under both normal and emergency conditions.

This chapter introduces these principles at diploma level. Detailed design must always be checked against the applicable national building regulations, water authority requirements, and recognized standards such as NFPA, EN, or other locally adopted codes. The numerical methods presented here are engineering tools for understanding and preliminary assessment; they do not replace an approved design.

Learning Objectives

By the end of this chapter, the learner should be able to:

  1. Describe mains, tanks, reservoirs, hydrants, valves and fire-pump arrangements.
  2. Distinguish static pressure, residual pressure, flow, head and water volume.
  3. Calculate pressure head, elevation loss, friction loss and pump power using appropriate equations.
  4. Explain the operation and selection of centrifugal, diesel and electric fire pumps.
  5. Interpret a simple pump curve and system-demand relationship.
  6. Evaluate water-supply reliability using capacity, redundancy, testing and maintenance criteria.
  7. Identify common hydraulic and operational failures and recommend controls.

1. Water-Supply Sources and Storage

1.1 Public mains

A public water main may serve fire hydrants, automatic sprinkler systems, or a private fire-service connection. Its advantages are continuous replenishment and low on-site storage requirements. Its limitations include variable pressure, dependence on municipal infrastructure, restricted flow during peak demand, water-main repairs, and possible isolation by utility valves.

A mains supply should be assessed using actual flow and pressure data rather than nominal pipe size alone. Important questions include:

  • What pressure is available at the point of connection?
  • What flow can be maintained while the fire demand is flowing?
  • Is the supply single-fed or looped?
  • Can a utility shutdown interrupt the fire supply?
  • Are backflow prevention, metering or pressure-reducing devices present?

Static pressure is pressure measured with no water flowing. Residual pressure, also called flowing pressure, is pressure measured while a specified flow is being discharged. Residual pressure is normally the more important design value because friction and other losses occur during operation.

1.2 Private mains and ring networks

Large sites often use a private underground fire main supplied by tanks and pumps. A ring main allows water to reach a hydrant or sprinkler riser from two directions, reducing the effect of a single pipe section being isolated. Sectional control valves divide the ring into manageable zones. Valves must be supervised, clearly identified and accessible.

A ring does not automatically guarantee reliability. If two adjacent valves are closed, a section may be isolated. Corrosion, poor drainage, traffic loading, freezing, or undocumented modifications may also reduce performance.

1.3 Tanks and reservoirs

A fire tank stores water for a specified fire demand and duration. Tanks may be above ground, underground, concrete, steel, sectional, or purpose-built composite units. A reservoir may be a larger open or closed storage body serving a site or community.

The effective fire volume is not always the geometric tank volume. Unusable volume below the pump suction, sediment allowance, water reserved for other services, and requirements for an air gap or structural freeboard must be considered. A simple storage relationship is:

Vrequired = Qdemand × t

where Vrequired is required usable volume in m³, Qdemand is the design flow in m³/s, and t is the required duration in seconds. If flow is expressed in L/min, it must first be converted: 1 L/min = 0.00001667 m³/s approximately.

For a demand of 2,000 L/min operating for 60 minutes:

Q = 2000 ÷ 1000 ÷ 60 = 0.0333 m3/s

Vrequired = 0.0333 × 3600 ≈ 120 m³

Thus, approximately 120 m³ of usable water is required before allowances for unusable volume and other mandated reserves.

Tanks require level indication, low-level alarm, overflow protection, drain arrangements, access covers, inspection provisions and protection from contamination. A tank that is physically full but has a blocked suction, frozen inlet, closed valve or excessive sediment cannot be treated as a reliable supply.

1.4 Suction arrangements

A pump may draw from a suction tank through a flooded suction, where water stands above the pump inlet, or through a lift arrangement, where the pump must raise water from a lower level. Flooded suction is generally more reliable because it reduces the possibility of air entry and cavitation.

The suction pipe should be short, properly supported, adequately sized and arranged to avoid air pockets. Eccentric reducers are commonly installed with the flat side uppermost on horizontal pump suction piping to reduce air accumulation. Suction strainers, if used, must not become blocked and must be suitable for the required flow.

2. Hydrants, Valves and Fire-Service Fittings

2.1 Hydrants

Hydrants provide water for fire-service hose lines and, in some systems, for testing. Common arrangements include pillar hydrants above ground and flush hydrants below ground. A hydrant installation normally includes an isolation valve, outlet connections, caps, drainage or frost protection, and clear access.

Hydrant spacing and flow requirements depend on building occupancy, fire-service practice, local regulations and the reach of hose streams. A hydrant should not be located where parked vehicles, stored goods, gates or falling building elements can obstruct access. Hydrants must be identifiable in darkness and protected from impact where necessary.

Hydrant flow testing measures both flow and residual pressure. A high static pressure with a large pressure drop during flow may indicate an undersized main, excessive friction, a partially closed valve, or insufficient source capacity.

2.2 Valves

Important fire-service valves include:

Valve or fittingMain functionTypical control concern
Isolation valveSeparates a pipe sectionMust remain open and supervised
Check valvePrevents reverse flowCan cause loss if stuck or incorrectly installed
Alarm check valveControls wet-pipe alarm operationRequires correct trim and maintenance
Pressure-reducing valveLimits downstream pressureMust be tested under flow
Pressure-relief valvePrevents excessive pressureDischarge must be safely managed
Deluge valveReleases water to open nozzlesMust operate rapidly and reset correctly
Test-and-drain valvePermits functional testing and drainageMust discharge safely

A valve position indicator or supervisory switch provides evidence that an isolation valve has not been closed. Locked-open or electrically supervised arrangements are common controls, but supervision does not replace physical inspection.

3. Fire Pumps and Pump Assemblies

3.1 Purpose and operating principle

A fire pump adds energy to water so that the required flow reaches the hydraulically remote or most demanding point at the required pressure. Most fire pumps are centrifugal pumps. An impeller increases water velocity, and the casing converts part of that velocity into pressure.

A typical pump assembly may include a suction pipe, suction control valve, pump, driver, discharge check valve, discharge isolation valve, pressure gauges, test header or flow-meter arrangement, controller, sensing line, and a pressure-maintenance pump.

3.2 Main pump types

An electric-motor-driven pump has a rapid start and relatively simple operation, but it depends on a reliable electrical supply. The electrical feeder should be dedicated or suitably protected, and the controller should be located where it is protected from fire and flooding.

A diesel-engine-driven pump provides independence from the normal electrical supply. It requires fuel, batteries, cooling, exhaust arrangements, ventilation and regular engine testing. Fuel deterioration, discharged batteries and inadequate ventilation are common failure causes.

A jockey pump, or pressure-maintenance pump, is a small pump that compensates for minor leakage and pressure fluctuations. It is not intended to supply the main fire demand. Its start and stop settings must be coordinated so that it does not mask a real system demand or cause excessive cycling.

Vertical turbine pumps may be used where the water level is below the pump discharge head. Horizontal split-case pumps are widely used for larger flows and accessible maintenance. End-suction pumps may be suitable for smaller systems where permitted by the governing standard.

3.3 Pump curve and system curve

A pump curve relates flow to developed head at a specified speed and impeller diameter. As flow increases, the head produced by a centrifugal pump commonly decreases. The system curve represents the head required by the pipe network at different flows. The operating point occurs where the pump curve and system curve intersect.

The required pump head can be expressed as:

Hp = Hstatic + hf + hminor + Hrequired

where Hp is pump head, Hstatic is elevation head or static lift, hf is straight-pipe friction loss, hminor is fitting and valve loss, and Hrequired is the pressure head needed at the outlet or remote device. All terms are expressed in metres of water.

A pump should not merely have a high shutoff pressure. It must deliver the required rated flow at the required pressure, and the complete pump, driver and controller must be acceptable for fire-service use. Excessive pressure can damage components, cause unsafe hose reaction forces and activate relief devices.

4. Fundamental Hydraulic Quantities

4.1 Flow and continuity

Flow rate is the volume passing a point per unit time:

Q = V ÷ t

where Q is flow rate in m³/s, V is volume in m³, and t is time in seconds.

For steady flow in a full pipe, continuity gives:

Q = A × v

where A is internal cross-sectional area in m² and v is mean velocity in m/s. For a circular pipe:

A = πD² ÷ 4

where D is the internal diameter in metres. The inside diameter, not the nominal trade size, should be used for calculations.

4.2 Pressure and pressure head

Pressure is force per unit area. In water systems, pressure may be reported in kPa, bar, psi or metres of water. The relationship between pressure and pressure head is:

Hp = p ÷ (ρg)

where Hp is pressure head in m, p is pressure in Pa, ρ is water density in kg/m³, and g is gravitational acceleration, approximately 9.81 m/s². For ordinary water, 1 m of water is approximately 9.81 kPa, and 100 kPa is approximately 10.2 m of water.

The hydrostatic pressure difference caused by elevation is:

∆p = ρg∆z

where ∆z is the vertical elevation difference. A discharge point higher than the source consumes pressure; a lower point gains pressure. In practical fire calculations, elevation loss is approximately 0.0981 bar per metre of rise.

4.3 Bernoulli energy relationship

For steady, incompressible flow along a streamline, the extended Bernoulli equation is:

p₁ ÷ (ρg) + z₁ + v₁² ÷ (2g) + Hp = p₂ ÷ (ρg) + z₂ + v₂² ÷ (2g) + hL

Here, subscripts 1 and 2 identify two locations; p is pressure, z is elevation, v is velocity, Hp is pump head added, and hL is total head loss. The equation assumes a representative mean velocity and accounts for friction and local losses through hL.

5. Friction and Local Losses

5.1 Darcy–Weisbach equation

For a full pipe, the Darcy–Weisbach equation is:

hf = f × (L ÷ D) × (v² ÷ 2g)

where hf is friction head loss in m, f is the dimensionless Darcy friction factor, L is pipe length in m, D is internal diameter in m, v is mean velocity in m/s, and g is 9.81 m/s². It applies to fully developed internal flow and requires a suitable friction factor based on Reynolds number and relative roughness.

The Reynolds number is:

Re = ρvD ÷ μ

where μ is dynamic viscosity in Pa·s. Laminar flow generally occurs below approximately Re = 2300, while fire-system pipe flow is usually turbulent. For turbulent flow, f depends on roughness and Reynolds number. The Colebrook–White relationship is one accepted method, although charts or approved software are normally used in practice.

5.2 Hazen–Williams method

Fire-service calculations frequently use the empirical Hazen–Williams equation for water in commercial pipes. In SI form, one commonly used expression is:

hf = 10.67 × L × Q1.852 ÷ (C1.852 × D4.87)

where hf is loss in m, L is length in m, Q is flow in m³/s, D is internal diameter in m, and C is the dimensionless Hazen–Williams roughness coefficient. The equation is empirical, applies primarily to water, and should be used with the coefficient and unit convention specified by the adopted code or design standard. It should not be mixed with a different unit form.

5.3 Minor losses

Bends, tees, entrances, exits, strainers, valves and fittings produce local losses. The general loss expression is:

hminor = K × v² ÷ (2g)

For several fittings:

hminor,total = ∑K × v² ÷ (2g)

where K is the dimensionless local-loss coefficient. Some fire standards use equivalent length or tabulated fitting losses instead. The methods should not be double-counted: if a fitting loss is already included in an equivalent length, it must not also be added separately.

6. Worked Hydraulic Examples

Example 1: Velocity and pressure head

A 100 mm internal-diameter pipe carries 1,000 L/min. Determine the approximate velocity.

Convert flow:

Q = 1000 ÷ 1000 ÷ 60 = 0.01667 m3/s

Pipe area:

A = π(0.1)2 ÷ 4 = 0.00785 m2

Velocity:

v = Q ÷ A = 0.01667 ÷ 0.00785 ≈ 2.12 m/s

The result is a mean velocity. Actual design acceptability depends on the governing standard, pipe material, noise, water hammer and available pressure.

Example 2: Elevation loss

A hydrant is 18 m above the pump discharge. The pressure reduction due to elevation is:

∆p = ρg∆z = 1000 × 9.81 × 18 = 176,580 Pa ≈ 176.6 kPa

Thus, elevation alone consumes approximately 176.6 kPa, or 1.77 bar, before friction and fitting losses are considered.

Example 3: Darcy–Weisbach friction loss

Water flows at 2.0 m/s through 80 m of 100 mm internal-diameter pipe. Assume a Darcy friction factor of 0.020. Determine the friction loss.

hf = 0.020 × (80 ÷ 0.10) × (2.0² ÷ (2 × 9.81))
hf = 0.020 × 800 × 0.2039 ≈ 3.26 m

The friction loss is approximately 3.26 m of water, equivalent to about 32.0 kPa. The calculation is valid only if the assumed friction factor is appropriate for the pipe roughness and flow regime.

7. Water-Supply Reliability

Reliability means more than having a large pump or tank. It is the probability that the complete supply will deliver the required flow and pressure when demanded. Reliability should be evaluated as a chain:

  1. Source availability: Is water present and replenished?
  2. Storage capacity: Is sufficient usable volume available for the required duration?
  3. Suction integrity: Can water reach the pump without air entry or blockage?
  4. Pump capability: Can the pump meet the demand at the actual flow?
  5. Driver availability: Will electricity or diesel power be available?
  6. Distribution integrity: Are pipes, valves and fittings open and undamaged?
  7. Control operation: Will detection, release and pump-start systems operate?
  8. Maintenance readiness: Have inspection and testing identified defects?

A useful preliminary water-balance expression is:

Vavailable = Vinitial + Vreplenished − Vreserved − Vunusable

The supply is adequate for a demand duration when Vavailable ≥ Qdemand × t, subject to code requirements and assumptions about replenishment. Replenishment should not be credited unless the incoming supply is demonstrably reliable during the incident.

Reliability is improved by independent power arrangements, automatic pump starting, duplicate pumps where required, looped mains, supervised valves, protected tanks, emergency access, tested alarms and documented impairment procedures. Redundancy must be genuine: two pumps sharing one failed controller, one fuel source or one suction pipe may not provide independent protection.

8. Testing, Inspection and Maintenance

Routine testing should confirm both readiness and performance. Typical activities include:

  • checking tank level, temperature and physical condition;
  • verifying valve position and supervisory signals;
  • running electric and diesel pumps under no-flow and flow conditions as required;
  • checking pump suction and discharge pressures;
  • testing automatic start from pressure drop or system demand;
  • inspecting diesel fuel, batteries, cooling and exhaust systems;
  • flowing hydrants and test headers safely;
  • inspecting strainers, drains, alarm devices and pressure gauges;
  • recording results, defects, corrective actions and responsible persons.

A test that starts a pump but does not measure flow may fail to reveal a blocked discharge, worn impeller, closed valve or inadequate source. Test instruments must be calibrated or checked, and results should be compared with baseline data. A gradual reduction in flow at the same pressure can indicate deterioration before complete failure occurs.

Any impairment—such as a closed valve, drained tank, unavailable pump or isolated main—should be formally controlled. The responsible person should assess affected areas, notify stakeholders, provide temporary measures where necessary, restrict ignition hazards if appropriate, and restore the system promptly.

9. Illustrative Case Study: Warehouse Ring Main

Background

A fictional, illustrative distribution warehouse has a sprinkler system and four external hydrants. Water is supplied from a 150 m³ tank through an electric fire pump. The design fire demand is 1,800 L/min for 60 minutes. The remote sprinkler riser is 12 m above the pump and requires 500 kPa residual pressure at the design flow.

Problem

During an acceptance test, the pump starts correctly, but the remote riser pressure is only 410 kPa. Static pressure before the test was 720 kPa. The tank level was satisfactory.

Analysis

Required volume is:

Vrequired = 1.8 m3/min × 60 min = 108 m3

The tank has nominally sufficient volume, although usable volume and any reserve must be confirmed. The pressure shortfall is 90 kPa. The 12 m elevation consumes approximately:

12 × 9.81 = 117.7 kPa

The investigation finds that one ring-main isolation valve is not fully open and that a temporary test hose has a smaller internal diameter than specified. Both conditions increase loss. A pump test also shows that the pump produces the expected pressure at low flow but underperforms at the design flow, suggesting a combination of system restriction and pump deterioration.

Approach and solution

The facility isolates the impairment under its fire-safety procedure, opens and supervises the correct valve, removes the undersized hose, cleans the suction strainer and performs a calibrated flow test. The pump curve is compared with the original acceptance record. The pump is serviced, and the ring main is hydraulically tested from multiple points.

Outcome

The remote riser achieves the required residual pressure at the design flow. The facility updates valve identification, records the test baseline and adds a periodic flow-test review. The tank level is also revised to identify usable fire volume rather than total geometric volume.

Learning points

The case demonstrates that a pressure failure may arise from several interacting causes. Static pressure alone does not prove adequacy. Tank volume, pump performance, valve position, pipe friction, elevation and test configuration must be assessed together.

10. Challenges, Limitations and Professional Practice

Hydraulic calculations are sensitive to internal diameter, roughness, flow distribution, elevation data and fitting assumptions. Nominal pipe sizes may differ between materials. A calculation based on clean new pipe may overestimate performance after years of corrosion or deposits. A single-point flow test may not represent simultaneous sprinkler and hydrant operation.

Computer hydraulic models are useful for complex networks, but their results are only as good as the input data. The designer must verify pipe routes, elevations, valve status, demand nodes and pump curves. Software should support engineering judgement, not conceal uncertainty.

Water quality and environmental issues also matter. Fire tanks can become breeding sites or accumulate contaminants if neglected. Discharge from testing must not cause erosion, flooding or pollution. Diesel fuel storage requires spill control and safe handling. Unauthorized alteration of valves, pumps or alarm settings is a governance failure because it can silently reduce protection.

Contemporary systems increasingly use remote tank-level monitoring, pump-controller communication, digital maintenance records and condition-based alarms. These technologies improve visibility but introduce cybersecurity, power-supply and data-integrity concerns. A remote indication should not be accepted without a local verification method and a defined response procedure.

Best-Practice Design and Assessment Checklist

  • Establish the governing code, design hazard and required duration.
  • Confirm the design flow and required residual pressure at the hydraulically remote point.
  • Survey actual elevations and pipe internal diameters.
  • Separate static pressure from residual pressure.
  • Include elevation, straight-pipe friction and local losses.
  • Use one consistent hydraulic method and unit system.
  • Confirm pump duty at the required flow, not only at shutoff.
  • Verify tank usable volume, suction conditions and replenishment assumptions.
  • Protect and supervise critical valves.
  • Provide suitable test facilities and safe discharge routes.
  • Maintain independent records of inspection, testing and impairment.
  • Reassess the supply after building alterations, occupancy changes or water-main modifications.

Chapter Summary

Fire-suppression performance depends on a complete and reliable water-supply chain comprising a source, storage, suction arrangement, pump, distribution network, valves and discharge devices. Public mains, private mains, tanks and reservoirs each have advantages and failure modes. Hydrants must remain accessible and capable of delivering their required flow, while isolation, check, alarm, pressure-control and deluge valves must be correctly selected, supervised and maintained.

Hydraulic analysis uses flow continuity, pressure head, elevation relationships, Bernoulli energy balance and friction-loss equations. Darcy–Weisbach provides a general pipe-friction method, while Hazen–Williams is an empirical water-flow method commonly used in fire-service work under specified unit conventions. Local fitting losses and elevation can be as important as straight-pipe friction.

Fire pumps must be evaluated at their required duty point, with suitable drivers, controls, suction conditions and testing arrangements. Reliability requires adequate usable storage, genuine redundancy where required, dependable power, open valves, protected equipment and effective inspection and impairment control. Static pressure or a successful pump start alone cannot demonstrate system adequacy.

Key Terms

Water main: A pipe conveying water for public or private distribution.

Residual pressure: Pressure measured while water is flowing.

Static pressure: Pressure measured when there is no flow.

Fire tank: Dedicated storage providing water for fire protection.

Usable volume: The portion of stored water that can actually be delivered to the system.

Hydrant: A fixed outlet used to supply fire-service hose lines.

Isolation valve: A valve used to separate a section of pipe.

Check valve: A valve that prevents reverse flow.

Jockey pump: A small pressure-maintenance pump.

Centrifugal pump: A pump that transfers energy through a rotating impeller.

Pump head: Energy added by a pump, expressed as metres of water.

Flow rate: Volume passing a point per unit time.

Velocity: Mean speed of water through a pipe cross-section.

Elevation head: Pressure-equivalent height difference in a water system.

Friction loss: Energy lost through resistance along a pipe.

Minor loss: Energy lost at fittings, valves, entrances or exits.

Darcy friction factor: Dimensionless factor used in the Darcy–Weisbach equation.

Hazen–Williams coefficient: Empirical coefficient representing pipe-flow roughness.

Residual demand: Required pressure and flow during system operation.

Impairment: A condition in which a fire-protection component or function is unavailable or degraded.

Review Questions

Short Answer Questions

  1. Distinguish static pressure from residual pressure.
  2. State two advantages and two limitations of a public water main.
  3. What is the function of a jockey pump?
  4. Name the main terms included in a pump-head calculation.
  5. Why must fire valves be supervised or regularly checked?

Long Answer Questions

  1. Describe the components and operation of a typical tank-and-pump fire-water supply.
  2. Explain the Darcy–Weisbach equation and identify the factors affecting friction loss.
  3. Compare electric and diesel fire-pump drivers.
  4. Explain how hydrant flow testing can reveal deficiencies in a water supply.
  5. Discuss the factors that determine water-supply reliability.

Analytical / Application Questions

  1. A 125 mm internal-diameter pipe carries 1,500 L/min. Calculate the approximate mean velocity and explain whether additional design checks are required before accepting the result.
  2. A remote sprinkler point is 20 m above a pump and requires 450 kPa residual pressure. Calculate the minimum pressure head needed before adding friction and fitting losses.
  3. A tank contains 140 m³ of usable water and the design demand is 2,100 L/min for 60 minutes. Determine whether the volume is adequate, then discuss at least two reliability assumptions that must be verified.

Multiple Choice Questions with Answers

Question 1

Which pressure is normally most useful for evaluating performance while a fire system is operating?

A. Static pressure

B. Residual pressure

C. Atmospheric pressure

D. Vapour pressure

Correct Answer: B. Residual pressure

Question 2

A fire demand of 2,000 L/min operates for 60 minutes. What usable volume is required?

A. 20 m³

B. 60 m³

C. 120 m³

D. 2,000 m³

Correct Answer: C. 120 m³

Question 3

What is the primary function of a jockey pump?

A. To supply the complete sprinkler demand

B. To maintain pressure during minor leakage

C. To drain the fire tank

D. To prevent all friction loss

Correct Answer: B. To maintain pressure during minor leakage

Question 4

Which equation relates pipe flow rate, area and mean velocity?

A. Q = A × v

B. Q = A ÷ v

C. Q = v ÷ A

D. Q = ρgA

Correct Answer: A. Q = A × v

Question 5

Approximately how much pressure is lost through 10 m of vertical rise in a water system?

A. 0.098 kPa

B. 0.98 kPa

C. 9.81 kPa

D. 98.1 kPa

Correct Answer: D. 98.1 kPa

Question 6

In the Darcy–Weisbach equation, which quantity represents pipe length?

A. f

B. L

C. D

D. v

Correct Answer: B. L

Question 7

What does a check valve primarily prevent?

A. Forward flow

B. Reverse flow

C. Tank filling

D. Pressure measurement

Correct Answer: B. Reverse flow

Question 8

Which condition generally increases pipe friction loss?

A. Increasing pipe diameter while keeping flow constant

B. Reducing pipe length

C. Increasing flow rate

D. Smoothing the pipe interior

Correct Answer: C. Increasing flow rate

Question 9

A pump operating point is found where which two relationships intersect?

A. Tank curve and valve curve

B. Pump curve and system curve

C. Pressure curve and temperature curve

D. Hydrant curve and fuel curve

Correct Answer: B. Pump curve and system curve

Question 10

A tank has 140 m³ usable volume and demand is 2,100 L/min for 60 minutes. Is the volume adequate?

A. No; 21 m³ is required

B. No; 126 m³ is required

C. Yes; 126 m³ is required

D. Yes; 210 m³ is required

Correct Answer: C. Yes; 126 m³ is required

Fire Suppression Systems
Chapter 4 of 15