Electrical Energy Efficiency and Power SystemsIntroductionElectrical energy efficiency is the provision of the required service—mechanical output, fluid flow, compressed air, lighting, or production—using the least practical electrical energy. In an industrial facility, efficiency is not determined by one item alone. Transformer losses, motor loading, variable-speed control, pump and fan selection, compressed-air leakage, power factor, harmonics, voltage quality, peak demand, and distribution design interact continuously. Energy auditing therefore requires a systems perspective. Replacing an inefficient motor may produce little benefit if the motor is oversized, throttling is used to control a variable flow, or the driven machine operates unnecessarily. Conversely, a relatively small electrical loss can be important when it occurs continuously at high utilization. This chapter develops the principles and calculations needed to assess major electrical conservation opportunities and to convert measurements into technically sound recommendations. Learning ObjectivesAfter studying this chapter, the reader should be able to: - Explain the sources of losses in transformers, motors, drives, and distribution systems.
- Calculate electrical input, output, efficiency, power factor, energy, and demand.
- Select and evaluate efficiency measures for pumps, fans, and compressed-air systems.
- Diagnose the effects of poor power factor, harmonics, voltage variation, and imbalance.
- Estimate savings, demand reduction, and simple payback while recognizing measurement limitations.
- Prepare an integrated electrical conservation plan for an industrial facility.
1. Energy, Power, Demand, and EfficiencyPower is the rate of energy transfer. Electrical energy consumed over a period is commonly measured in kilowatt-hours (kWh), while maximum or interval-average power is measured in kilowatts (kW). Utilities may charge separately for energy and maximum demand. For a constant load, E = P t where E is energy in kWh, P is average power in kW, and t is time in hours. For a varying load, energy is the integral of power over time: E = ∫₀ᵀ P(t) dt In practical audits, interval meters usually approximate this integral by summing readings over fixed intervals. Demand is generally the highest average power recorded during a specified utility interval, such as 15 or 30 minutes; it is not necessarily the instantaneous peak. Efficiency is the ratio of useful output to input: η = Pout / Pin where η is dimensionless, P_out is useful output power, and P_in is input power. When expressed as a percentage, multiply η by 100. The definition must identify the system boundary. Motor efficiency may refer to shaft output divided by electrical input, whereas a pumping-system efficiency may include the motor, drive, pump, and hydraulic output. An energy conservation measure should be evaluated using measured operating conditions, operating hours, tariff structure, maintenance requirements, safety, and production constraints—not nameplate efficiency alone. 2. TransformersA transformer transfers alternating-current electrical energy between voltage levels through electromagnetic induction. Its principal losses are: - Core or no-load losses: hysteresis and eddy-current losses in the magnetic core. These occur whenever the transformer is energized and are approximately constant at rated voltage and frequency.
- Winding or load losses: resistive I²R losses in primary and secondary windings. These increase approximately with the square of load current.
- Stray-load losses: leakage flux induces currents in structural parts and windings.
- Dielectric and auxiliary losses: usually smaller, but relevant in large units.
A useful approximate model is Ploss = P₀ + PFL x² where P_loss is total loss, P₀ is no-load loss, P_FL is full-load load loss, and x is the fraction of rated apparent power. This relation assumes approximately constant voltage and frequency and uses load loss specified at the relevant reference temperature. Transformer efficiency is ηT = Pout / (Pout + P₀ + PFL x²) For a transformer supplying a load at power factor cos φ, Pout = Sr x cos φ where S_r is rated apparent power in kVA and P_out is in kW when S_r is expressed in kVA. Maximum efficiency occurs approximately when variable load loss equals no-load loss: P₀ = PFL x² Thus, x = √(P₀ / PFL) This condition is an analytical result, not a universal operating target. A transformer should not be deliberately overloaded to reach it, and voltage regulation, thermal limits, redundancy, and future growth must also be considered. Transformer audit measuresCommon measures include selecting a correctly sized high-efficiency transformer, de-energizing redundant units during low-load periods where operationally safe, improving load distribution among parallel transformers, correcting severe phase imbalance, cleaning cooling passages, and avoiding unnecessary overvoltage. Transformers should not be switched off merely to save no-load loss if doing so compromises reliability, protection coordination, or emergency readiness. Worked example. A 500 kVA transformer has no-load loss of 1.0 kW and full-load loss of 6.0 kW. At 60% loading and 0.90 power factor: x = 0.60 P_loss = 1.0 + 6.0(0.60)² = 3.16 kW P_out = 500(0.60)(0.90) = 270 kW η_T = 270/(270 + 3.16) = 0.9884, or approximately 98.84%. The example demonstrates that a small percentage loss can represent substantial annual energy when the transformer operates continuously. 3. Motors and Motor-Driven SystemsInduction motors convert electrical power into mechanical shaft power. Their losses include stator copper loss, rotor copper loss, core loss, friction and windage, and stray-load loss. Motor efficiency is: ηm = Pshaft / Pelectrical Motor selection must consider rated output, duty cycle, starting requirements, enclosure, environment, speed, load profile, and compatibility with a drive. A high-efficiency motor is not automatically economical if it is greatly oversized or operates only briefly. For a balanced three-phase motor, Pin = √3 VL IL cos φ where V_L is line-to-line RMS voltage in volts, I_L is line current in amperes, cos φ is displacement power factor, and P_in is watts. The formula assumes sinusoidal voltage and current and balanced three-phase operation. With significant harmonics, true power and true RMS measurements should be used rather than relying on simplified sinusoidal assumptions. Motor shaft output may be estimated as Pshaft = ηm √3 VL IL cos φ Motor audit steps include measuring current, voltage, power, power factor, operating hours, load variation, starts per hour, and temperature; comparing measured load with rated load; and checking whether the motor is controlled by throttling, dampers, bypasses, or mechanical transmission losses. Oversizing and rewindingA lightly loaded motor may have reduced efficiency and poor power factor, although the exact effect depends on motor design. Replacement should be justified by measured operating data, not current alone. Current can be misleading when voltage, power factor, harmonics, or load vary. Rewinding can be economical for a failed motor, but poor workmanship may increase losses, alter magnetic characteristics, reduce efficiency, or damage insulation. A procurement specification should require recognized efficiency classes, test data, warranty, and qualified repair facilities. 4. Variable-Speed DrivesVariable-speed drives (VSDs) regulate motor speed by controlling electrical frequency and voltage. They can provide major savings where the process demand varies, particularly for centrifugal pumps and fans. The drive itself introduces conversion losses and may create harmonics, common-mode voltage, bearing currents, electromagnetic interference, and motor insulation stress. For centrifugal machines operating under approximately similar conditions, the affinity laws are: Q₂/Q₁ = N₂/N₁ H₂/H₁ = (N₂/N₁)² P₂/P₁ = (N₂/N₁)³ where Q is flow, H is head, P is shaft power, and N is rotational speed. These relations apply approximately to geometrically similar operating conditions and do not replace the actual system curve or manufacturer data. System static head, fluid properties, viscosity, and control limits can make real savings substantially different. A VSD is most attractive when speed can be reduced while maintaining the required process output. It is less attractive when the load is nearly constant, when operation is predominantly at full speed, or when the drive causes unacceptable power-quality or reliability problems. A complete evaluation compares: - motor and drive efficiency over the actual load range;
- bypass and isolation arrangements;
- minimum safe speed and cooling requirements;
- harmonic mitigation and EMC compliance;
- control response and process stability;
- maintenance and lifecycle cost.
5. Pumps and FansPump and fan systems often waste energy because designers select excessive capacity and then control flow by throttling, damper closure, bypassing, or recirculation. These methods increase pressure loss without reducing the energy supplied by the motor proportionally. A hydraulic pumping power estimate is Ph = ρ g Q H where P_h is hydraulic power in watts, ρ is fluid density in kg/m³, g is gravitational acceleration in m/s², Q is flow in m³/s, and H is total head in metres. The electrical input is approximately Pe = ρ g Q H / (ηp ηm ηd) where η_p, η_m, and η_d are pump, motor, and drive efficiencies. If no drive is present, η_d may be taken as 1 in the simplified calculation. The equation assumes steady flow and uses total dynamic head, including elevation, pressure, velocity, and friction effects. An audit should develop the system curve, identify static and friction head, measure flow and pressure, inspect impeller size and wear, examine parallel-pump sequencing, and determine whether control valves or dampers are unnecessarily dissipating energy. Correcting oversized impellers, reducing unnecessary pressure, repairing leaks, using automatic sequencing, and installing a properly selected VSD are typical measures. Worked example: pump energyWater is pumped at Q = 0.050 m³/s through a total head of 30 m. Let ρ = 1000 kg/m³, g = 9.81 m/s², pump efficiency η_p = 0.78, motor efficiency η_m = 0.92, and drive efficiency η_d = 0.97. P_h = 1000 × 9.81 × 0.050 × 30 = 14,715 W = 14.715 kW. P_e = 14.715/(0.78 × 0.92 × 0.97) ≈ 21.2 kW. If the pump operates 4,000 h/year, annual electrical energy is approximately 84,800 kWh. A 10% reduction in electrical input at unchanged operating hours would save about 8,480 kWh/year, subject to verification that flow and pressure requirements remain satisfied. 6. Compressed-Air SystemsCompressed air is a high-cost utility because energy passes through the motor, compressor, cooling system, air treatment, distribution network, and end use. Important losses arise from leaks, excessive pressure, artificial demand, inappropriate open blowing, poor compressor sequencing, blocked filters, pressure drops, and operation during unproductive periods. A leakage survey should use ultrasonic detection, temperature and pressure observations, maintenance records, and a controlled off-production test. If a compressor supplies air to a closed system and pressure decays at a known rate, leakage can be estimated from the measured decay and receiver volume, although compressor controls and multiple receivers complicate the calculation. The ideal isothermal compression work for compressing a fixed mass of ideal gas from absolute pressure p₁ to p₂ is represented by W = p₁ V₁ ln(p₂/p₁) where W is work, p₁ and p₂ are absolute pressures, V₁ is initial volume, and ln is the natural logarithm. This is a theoretical reference, not a direct prediction of compressor electricity use. Real compressors require additional work because of inefficiency, heat transfer, pressure pulsation, motor losses, and treatment equipment. Best practices include repairing leaks promptly, lowering header pressure to the minimum acceptable value, eliminating inappropriate uses, replacing compressed-air cooling or open blowing with dedicated blowers where suitable, using storage correctly, cleaning filters, and sequencing compressors to match demand. Pressure must always be stated as gauge or absolute; gas-compression equations require absolute pressure. 7. Power Factor and Reactive PowerIn a sinusoidal single-phase circuit, apparent power is S = VI, real power is P = VI cos φ, and reactive power is Q = VI sin φ. In a balanced three-phase circuit: S = √3 VL IL P = √3 VL IL cos φ Q = √(S² − P²) S is in VA, P in W, and Q in var. The power factor is P/S for sinusoidal waveforms. With distortion, the true power factor is real power divided by total RMS apparent power; it includes both displacement and distortion effects. For a known real power P and initial and target displacement power factors pf₁ and pf₂, the capacitor reactive-power requirement is approximately Qc = P(tan φ₁ − tan φ₂) where φ₁ = cos⁻¹(pf₁) and φ₂ = cos⁻¹(pf₂). This relation assumes sinusoidal conditions and neglects capacitor losses and voltage changes. Example. A 100 kW load operates at 0.75 power factor. The desired power factor is 0.95. φ₁ = cos⁻¹(0.75), φ₂ = cos⁻¹(0.95) Q_c ≈ 100[tan(φ₁) − tan(φ₂)] ≈ 55.3 kvar. A practical capacitor bank would be selected using standard steps, automatic control, detuning requirements, and measured operating conditions. Overcorrection can produce leading power factor, excessive voltage, or resonance. Capacitors must not be installed without checking harmonics and switching transients. Improving power factor reduces current for a given real power and therefore reduces upstream I²R losses and voltage drop. It may also reduce utility demand or reactive-power charges. It does not reduce the real energy required by an ideal constant-output motor by itself. 8. Harmonics and Power QualityA nonsinusoidal waveform can be represented as a fundamental component plus harmonic components. Harmonic order h is the component frequency divided by the fundamental frequency. Six-pulse rectifiers, VSDs, switch-mode power supplies, and arc equipment are common sources. Voltage total harmonic distortion is commonly defined as THDV = √(V₂² + V₃² + …) / V₁ and current THD similarly as THDI = √(I₂² + I₃² + …) / I₁ where V₁ and I₁ are fundamental RMS components and V_h and I_h are harmonic components. The measurement bandwidth and standard definition must be stated. Some standards use total RMS current in the denominator for a distortion factor, so terminology should not be mixed. Consequences include transformer heating, neutral overloading from triplen harmonics, capacitor resonance, nuisance tripping, motor torque pulsation, additional losses, and interference with sensitive equipment. Mitigation may involve low-harmonic drives, passive or active filters, line reactors, phase-shifting transformers, suitable transformer connections, separation of sensitive loads, and proper neutral sizing. Power-quality investigations should record RMS voltage, sag, swell, interruption, imbalance, frequency, transients, flicker, harmonics, and event duration using calibrated instruments. A correlation with process events is essential; not every disturbance originates within the facility. 9. Distribution Losses and Voltage ImbalanceConductor losses are approximately Ploss = I² R for each conductor, where I is RMS current and R is conductor resistance at operating temperature. Total feeder loss is obtained by summing the losses of all conductors and relevant equipment. Larger conductors, shorter routes, balanced loading, correct joints, and higher distribution voltage can reduce losses, subject to installation standards and protection requirements. For a balanced three-phase load, increasing power factor reduces current according to I = P/(√3 VL pf) for real power P, line voltage V_L, and power factor pf. Thus, at unchanged P and V, current is inversely proportional to power factor. Voltage imbalance is particularly harmful to motors. The percentage voltage unbalance is often calculated as % unbalance = 100 × maximum deviation from average voltage / average voltage The exact definition should follow the applicable standard. Even a small voltage imbalance can create a much larger negative-sequence current and substantial motor heating. Causes include uneven single-phase loading, loose connections, unequal transformer impedances, and utility conditions. 10. Peak Demand ManagementPeak demand charges can be reduced without reducing annual production by shifting flexible loads, staggering motor starts, rescheduling batch processes, controlling electric heating, using storage, and preventing simultaneous operation of large equipment. Demand control must not create unsafe cycling, poor product quality, or process interruptions. A demand profile should be plotted at the utility interval length. The audit should identify the equipment responsible for the top intervals, distinguish coincident from noncoincident loads, and quantify the production impact of each control option. A short instantaneous peak may not affect the bill if the tariff uses interval-average demand, while a sustained moderate load can be financially significant. 11. Integrated Audit MethodA professional electrical audit follows a measurement-based sequence: - Define scope: establish boundaries, production requirements, tariffs, safety rules, and reporting period.
- Collect records: obtain bills, one-line diagrams, equipment schedules, maintenance data, operating hours, and production levels.
- Conduct a walk-through: identify motors, transformers, drives, pumps, fans, compressors, capacitors, harmonic sources, and abnormal heating.
- Measure: use calibrated power analyzers, clamp meters, flow meters, pressure gauges, tachometers, and temperature instruments. Observe representative operating states.
- Construct energy balances: compare utility input with major loads and estimate unexplained losses.
- Develop measures: separate no-cost, low-cost, retrofit, and capital measures; identify interactions.
- Calculate savings: include kWh, kW, power factor charges, maintenance, production effects, and implementation costs.
- Verify: establish a baseline and use measurement and verification procedures after implementation.
Simple payback is SPB = initial investment / annual net savings where both numerator and denominator use consistent currency units. It is easy to understand but ignores discounting, residual value, degradation, taxes, and risk. Life-cycle cost analysis is preferable for major equipment. 12. Illustrative Case Study: Manufacturing FacilityBackground. This illustrative case concerns a medium-sized food-processing plant operating 6,000 h/year. Its electricity bill shows a high maximum demand. The plant has two large refrigeration compressors, several constant-speed pumps, exhaust fans controlled by dampers, a compressed-air network, and a 1,000 kVA transformer. Problem. The energy team initially proposed replacing all motors with premium-efficiency models. A preliminary survey, however, found that many motors were lightly loaded, pumps were throttled, compressed-air pressure was higher than necessary, and capacitors were connected near harmonic-producing drives. Analysis. A two-week monitoring program measured feeder power, demand intervals, motor loads, pump flow and pressure, compressor loading, air pressure, leakage during shutdown, transformer temperature, and harmonic spectra. The results showed: - pump flow varied substantially while pump speed remained constant;
- fan dampers dissipated pressure during low-production periods;
- compressed-air leakage represented a continuous base load;
- capacitor switching caused resonance near a dominant drive harmonic;
- the transformer was safe thermally but operated with avoidable no-load loss during weekend shutdowns.
Approach. The plant adopted a staged solution: - repair compressed-air leaks and reduce header pressure after confirming end-use requirements;
- install VSD control on one variable-flow pump and one exhaust fan, with minimum-speed safeguards;
- revise compressor sequencing and eliminate open-air cleaning where alternatives were safe;
- replace the capacitor bank with a detuned, automatically controlled system after a harmonic study;
- rebalance single-phase loads and tighten distribution connections under an approved safety procedure;
- switch the redundant transformer out during scheduled shutdowns, retaining emergency supply capability;
- specify efficiency, harmonic compatibility, and measured performance in future procurements.
Outcome. Post-implementation monitoring verified lower average kW, reduced demand peaks, more stable voltage, and lower compressed-air consumption while production output was maintained. The most important lesson was that system control and operating practice produced greater value than indiscriminate motor replacement. Savings were accepted only after comparing production-normalized energy use with the established baseline. Learning points. The case demonstrates that an audit must examine the service delivered, not merely the efficiency label of individual components. It also demonstrates that power factor correction, drives, and harmonic mitigation must be evaluated together. 13. Limitations, Safety, and GovernanceElectrical conservation measures can create hazards if implemented without engineering review. Capacitor banks can store lethal energy and may resonate with system inductance. VSDs require suitable isolation, grounding, motor insulation evaluation, and electromagnetic-compatibility controls. Measurement personnel must follow lockout/tagout, arc-flash, PPE, and energized-work procedures. Recommendations should comply with applicable electrical codes, utility rules, equipment standards, occupational-safety requirements, and manufacturer instructions. Data governance is also important: interval-meter data may reveal production schedules and must be controlled appropriately. Energy savings should not be claimed by changing the baseline, reducing product quality, or shifting energy to an unmetered process. Artificial intelligence can assist with load forecasting, anomaly detection, motor-fault classification, and optimization of demand response. It does not replace calibrated measurement, engineering judgment, cybersecurity controls, or responsibility for safe operation. Models should be validated against operating changes and should provide an auditable basis for recommendations. Best-Practice Checklist- Define the useful service before calculating efficiency.
- Measure real power, apparent power, power factor, harmonics, and operating conditions.
- Use system curves for pumps and fans rather than relying only on nameplate data.
- Check the complete motor-drive-load chain.
- Treat compressed air as an expensive utility and control leaks and pressure.
- Investigate harmonics before installing capacitors.
- Analyze demand at the tariff interval length.
- Include distribution, transformer, and standby losses.
- Evaluate safety, reliability, maintainability, and production constraints.
- Verify savings after implementation using a documented baseline.
Chapter SummaryElectrical energy efficiency is a systems problem involving conversion, distribution, control, and end use. Transformer losses consist mainly of nearly constant core losses and load-dependent winding losses. Motor assessment requires measured load, efficiency, power factor, duty cycle, and driven-equipment requirements. Variable-speed drives can provide substantial savings in variable-torque applications, but their losses and power-quality effects must be considered. Pump and fan energy depends strongly on flow, head, and speed; throttling and bypass control often waste energy. Compressed-air systems require leak management, pressure optimization, correct sequencing, and elimination of inappropriate uses. Power factor correction reduces current and upstream losses but must be coordinated with harmonic analysis. Harmonics can cause heating, resonance, neutral overloading, and interference. Distribution losses vary with current squared, while voltage imbalance can severely affect motors. A sound audit combines bills, drawings, field inspection, calibrated measurements, engineering calculations, economic analysis, safety review, and post-installation verification. The best conservation measure is the one that reduces total lifecycle energy and cost while preserving safety, reliability, quality, and production performance. Key TermsTransformer no-load loss: Core loss present when a transformer is energized, largely independent of load. Load loss: Transformer loss that varies approximately with the square of load current. Motor efficiency: Shaft mechanical output divided by electrical input. Variable-speed drive: Power-electronic equipment that controls motor speed and torque. Affinity laws: Approximate relations connecting speed with flow, head, and power in centrifugal machines. System curve: Relationship between flow and total head required by a fluid system. Compressed-air leakage: Unintended escape of compressed air from a distribution or end-use system. Power factor: Ratio of real power to apparent power. Reactive power: Alternating energy exchange associated with electric and magnetic fields. Apparent power: Product of RMS voltage and current, measured in VA or kVA. Harmonic: Sinusoidal component whose frequency is an integer multiple of the fundamental frequency. THD: Total harmonic distortion relative to a stated fundamental or RMS reference. Voltage unbalance: Unequal three-phase voltage magnitudes, expressed according to a defined method. Distribution loss: Electrical energy converted mainly into heat in conductors and equipment. Peak demand: Highest measured average power over the utility demand interval. Energy baseline: Defined reference energy performance used for comparison. Measurement and verification: Process of determining and confirming actual savings. Life-cycle cost: Total ownership cost including capital, energy, maintenance, and disposal effects. Review QuestionsShort Answer Questions- Distinguish between transformer no-load loss and load loss.
- Why can a variable-speed drive save energy in a centrifugal pump system?
- Define true power factor and explain how it differs from displacement power factor.
- State two harmful effects of harmonics in an industrial electrical system.
- Why must compressed-air pressure be stated as gauge or absolute in gas calculations?
Long Answer Questions- Explain the procedure for auditing a motor-driven pump system, including measurements, calculations, and conservation options.
- Discuss the technical and economic considerations in selecting and applying capacitor banks for power-factor improvement.
- Explain the major losses in transformers and derive the approximate condition for maximum transformer efficiency.
- Describe how demand management can reduce electricity cost without reducing annual production.
- Develop an integrated electrical-efficiency program covering motors, drives, compressed air, distribution, harmonics, and verification.
Analytical / Application Questions- A balanced three-phase motor receives 400 V line-to-line, 50 A, at a power factor of 0.82 and has efficiency of 91%. Calculate electrical input power and shaft output power. State the assumptions used.
- A centrifugal fan operates at 100% speed and consumes 30 kW. If the required operating point can be met at 80% speed and the affinity laws are applicable, estimate the fan shaft power and discuss why actual electrical savings may differ.
- An industrial plant has a 250 kW real load at 0.70 power factor and wishes to reach 0.95. Estimate the required capacitor reactive power using the tangent relation, then identify two checks required before installation.
Multiple Choice Questions with AnswersQuestion 1Which transformer loss is present whenever the transformer is energized, even with no external load? A. Core or no-load loss B. Winding load loss only C. Mechanical friction loss D. Pump hydraulic loss Correct Answer: A. Core or no-load loss Question 2For a centrifugal pump under conditions where the affinity laws apply, reducing speed to 80% of its original value makes ideal shaft power approximately what fraction of the original? A. 80% B. 64% C. 51.2% D. 20% Correct Answer: C. 51.2% Question 3A balanced three-phase load has real power 100 kW, line voltage 400 V, and power factor 0.80. Approximately what line current flows? A. 100 A B. 181 A C. 250 A D. 312 A Correct Answer: B. 181 A Question 4What is the principal effect of improving power factor for a fixed real-power load and voltage? A. It increases required line current B. It reduces line current C. It eliminates all harmonic current D. It increases motor mechanical output automatically Correct Answer: B. It reduces line current Question 5Which equipment is a common source of electrical harmonics? A. Purely resistive heater B. Unloaded transformer only C. Variable-speed drive D. Mechanical pressure gauge Correct Answer: C. Variable-speed drive Question 6The approximate conductor loss relation P_loss = I²R indicates that doubling current, with resistance unchanged, will make the loss: A. Half as large B. Twice as large C. Three times as large D. Four times as large Correct Answer: D. Four times as large Question 7Which measure is generally most directly appropriate for reducing compressed-air energy waste? A. Increasing header pressure without testing B. Repairing leaks and eliminating inappropriate uses C. Operating all compressors continuously D. Opening additional blow-off valves Correct Answer: B. Repairing leaks and eliminating inappropriate uses Question 8In a pump power calculation, the expression ρgQH represents: A. Hydraulic power B. Motor efficiency C. Apparent electrical power D. Transformer no-load loss Correct Answer: A. Hydraulic power Question 9Why should harmonics be investigated before installing a large capacitor bank? A. Capacitors always reduce fundamental voltage to zero B. Capacitors can interact with system inductance and cause resonance C. Capacitors cannot supply reactive power D. Harmonics occur only in DC circuits Correct Answer: B. Capacitors can interact with system inductance and cause resonance Question 10A utility demand charge is commonly based on: A. The highest average power during a specified interval B. The lowest instantaneous current C. Total annual kWh divided by voltage D. Transformer nameplate kVA regardless of operation Correct Answer: A. The highest average power during a specified interval
|