Electrical Machines & Power Systems Laboratory

Chapter 3
Magnetic Circuits and Transformers

Bachelors Program in Electrical Engineering
Electrical Machines & Power Systems Laboratory   •   Bachelor

Magnetic Circuits and Transformers

Introduction and Context

Transformers are static electrical machines that transfer alternating-current power between circuits through mutual electromagnetic induction. They provide voltage conversion, galvanic isolation, impedance matching, measurement, and protection interfaces. Their operation depends on two linked ideas: the magnetic circuit establishes flux, while the electrical windings convert electrical energy to magnetic energy and back to electrical energy.

In the laboratory, transformer theory is connected to measurable quantities such as winding resistance, polarity, no-load current, equivalent impedance, voltage regulation, efficiency, excitation current, inrush current, and temperature. Correct testing requires safe procedures, appropriate instruments, and careful interpretation of nonideal behavior.

Learning Objectives

After completing this chapter, a student should be able to:

  1. Explain magnetic flux, magnetomotive force, reluctance, permeability, hysteresis, and saturation.
  2. Determine transformer polarity and identify additive and subtractive terminal relationships.
  3. Construct and interpret approximate and exact transformer equivalent circuits.
  4. Perform and analyze open-circuit and short-circuit tests.
  5. Calculate efficiency and voltage regulation.
  6. Explain autotransformer operation and its advantages and limitations.
  7. Analyze common three-phase transformer connections.
  8. Describe harmonics, inrush current, parallel operation, and transformer condition assessment.
  9. Apply laboratory safety, measurement, and diagnostic best practices.

1. Magnetic-Circuit Fundamentals

A magnetic circuit is a path followed by magnetic flux, usually through a ferromagnetic core and an air gap. The basic quantities are:

QuantitySymbolMeaning and unit
Magnetic fluxΦTotal magnetic field, weber (Wb)
Flux densityBFlux per unit area, tesla (T)
Magnetomotive forceℱMagnetic driving force, ampere-turns (A·turn)
Field strengthHMagnetizing force, A/m
ReluctanceℜOpposition to flux, A·turn/Wb
PermeabilityμAbility of a material to carry flux, H/m

For a uniform section of magnetic path,

B = Φ/A

where A is cross-sectional area in m². The constitutive relation is

B = μH

where μ = μ₀μᵣ, μ₀ is the permeability of free space and μᵣ is relative permeability. In ferromagnetic materials, μ is not constant; it changes with flux density and operating history.

Ampère’s law for a simple magnetic circuit is

ℱ = NI = ∮H dl

where N is the number of turns, I is current in amperes, and l is magnetic-path length in metres. The magnetic-circuit analogue of Ohm’s law is

Φ = ℱ/ℜ = NI/ℜ

with

ℜ = l/(μA)

These expressions apply most directly to a uniform, singly connected magnetic path. In a composite core, reluctances are combined in series or parallel, just as resistances are, provided leakage and fringing are treated appropriately.

The air gap often dominates reluctance because air has much lower permeability than steel. Consequently, a small gap can require substantial magnetizing current. Fringing causes the effective gap area to exceed the physical area, so simple calculations are approximate.

Hysteresis and Eddy-Current Losses

When a ferromagnetic core is cyclically magnetized, the B–H path forms a hysteresis loop. The loop area represents energy dissipated per cycle per unit volume. Hysteresis loss increases with frequency and maximum flux density. Eddy currents are induced in the conducting core by changing flux and produce I²R heating. Laminating the core and insulating adjacent laminations greatly reduces eddy-current paths.

Transformer cores are commonly made from grain-oriented silicon steel or, in high-frequency applications, ferrite. Core saturation occurs when additional magnetizing force produces only a small increase in flux density. Saturation sharply increases exciting current and waveform distortion.

2. Transformer Operating Principle

For a sinusoidal flux in a winding of N turns, Faraday’s law gives the rms induced emf:

E = 4.44 f N Φₘ

where E is rms emf in volts, f is frequency in hertz, and Φₘ is maximum flux in webers. The equation assumes sinusoidal flux and a uniformly distributed winding. For non-sinusoidal flux, the form factor differs from 4.44.

For an ideal transformer,

V₁/V₂ = N₁/N₂ = a

and

I₁/I₂ = N₂/N₁ = 1/a

where a is the turns ratio, primary quantities use subscript 1, and secondary quantities use subscript 2. Apparent power is conserved ideally:

V₁I₁ = V₂I₂

Real transformers have winding resistance, leakage reactance, core loss, magnetizing current, and finite mechanical and insulation strength.

Polarity and Dot Convention

The instantaneous polarity of induced voltages depends on winding orientation. The dot convention marks terminals that have the same instantaneous polarity when currents enter or leave according to the chosen reference directions. Polarity is established experimentally using a low-voltage source and a voltmeter, not by assuming that terminal labels are universal.

In a polarity test, connect one terminal of the primary to one terminal of the secondary, apply a safe low voltage, and measure the voltage across the two unconnected terminals. If the measured voltage is approximately the sum of the individual winding voltages, the connection is additive; if it is approximately their difference, it is subtractive. The test must use a source within the insulation and voltage rating of the equipment.

3. Transformer Equivalent Circuits

The exact equivalent circuit contains:

  • primary resistance R₁ and leakage reactance X₁;
  • shunt core-loss resistance Rc;
  • magnetizing reactance Xm;
  • secondary resistance R₂ and leakage reactance X₂.

The shunt branch represents excitation current. Rc models hysteresis and eddy-current losses, while Xm models the reactive magnetizing current. Leakage reactances represent flux that links one winding but not both.

To refer secondary quantities to the primary side, use

R₂′ = a²R₂, X₂′ = a²X₂, ZL′ = a²ZL

where primes denote referred quantities and ZL is the load impedance. The approximate series parameters are

Req = R₁ + R₂′
Xeq = X₁ + X₂′

The approximate circuit neglects the small voltage drop caused by excitation current when calculating loaded voltage. This is usually acceptable for distribution-transformer calculations but not for precise regulation or heavily loaded machines.

4. Laboratory Tests

Preliminary Safety and Instrumentation

Before energizing a transformer, inspect insulation, terminals, earth continuity, fuses, ratings, and test-lead condition. Use an isolation transformer or protected laboratory supply where appropriate. Begin with the variac at zero, keep the secondary unloaded unless the test requires a load, and never change connections on an energized circuit. A true-rms voltmeter is preferred when waveforms may be distorted. Record voltage, current, power, frequency, temperature, and instrument ranges.

Winding-Resistance Test

A dc resistance test determines winding resistance and detects poor joints, loose connections, or unequal phase resistance. Because winding resistance is temperature-dependent, measurements should be corrected only when the conductor material and reference temperature are known. For copper, a useful approximation is

RT = RT₀[1 + α(T − T₀)]

where α is approximately 0.00393 per °C near 20 °C, T is the measurement temperature, and T₀ is the reference temperature. The formula is an approximation over a moderate temperature range.

Open-Circuit Test

The open-circuit test is normally performed on the low-voltage winding, with the other winding open. Rated voltage and frequency are applied, and V₀, I₀, and P₀ are measured. Since the no-load current is small, copper loss is often neglected, so

P₀ ≈ Pcore

The no-load power factor is

cos φ₀ = P₀/(V₀I₀)

The exciting-current components are approximately

Ic = I₀ cos φ₀
Im = I₀ sin φ₀

and the shunt parameters referred to the test side are

Rc = V₀/Ic, Xm = V₀/Im

These equations assume sinusoidal voltage and negligible winding copper loss during the test. The measured wattmeter power includes core loss and a small amount of copper loss.

Short-Circuit Test

In the short-circuit test, one winding is shorted and a low voltage is applied to the other until rated current flows. The measured quantities Vsc, Isc, and Psc provide

Zeq = Vsc/Isc
Req = Psc/Isc²
Xeq = √(Zeq² − Req²)

Here Psc is approximately full-load copper loss because the applied voltage is small and core flux is correspondingly small. The square-root expression requires Z_eq ≥ R_eq and consistent rms units.

Worked Example: Test-Based Parameters

A single-phase transformer gives the following short-circuit results when rated current is 5 A: Vsc = 18 V and Psc = 45 W. Therefore,

Zeq = 18/5 = 3.60 Ω,

Req = 45/5² = 1.80 Ω,

Xeq = √(3.60² − 1.80²) = 3.12 Ω approximately.

Thus the referred series impedance is approximately 1.80 + j3.12 Ω. If the open-circuit test gives V₀ = 230 V, I₀ = 0.40 A, and P₀ = 20 W, then cos φ₀ = 20/(230 × 0.40) = 0.217. Hence Rc ≈ 230/(0.40 × 0.217) = 2.65 kΩ and Xm ≈ 230/[0.40√(1 − 0.217²)] = 0.59 kΩ. These values are approximate because the test data include instrument and nonideal effects.

5. Efficiency and Voltage Regulation

Transformer efficiency is

η = Pout/Pin × 100% = Pout/(Pout + Pcore + Pcu) × 100%

where output and losses are in watts. At a load fraction x of rated current, copper loss is approximately x²Pcu,FL, while core loss is nearly constant at fixed voltage and frequency:

ηx = xSr cos φ/[xSr cos φ + Pcore + x²Pcu,FL]

where Sr is rated apparent power in VA and cos φ is load power factor. Maximum efficiency occurs approximately when

Pcu = Pcore

This condition is useful but does not imply maximum efficiency at rated load.

Voltage regulation measures the change in secondary voltage from no load to load, with primary voltage held constant:

VR = (Vno-load − Vfull-load)/Vfull-load × 100%

An approximate regulation formula for a lagging load is

VR ≈ (I₂Req cos φ₂ + I₂Xeq sin φ₂)/V₂ × 100%

when all parameters are referred to the secondary side. For a leading power factor, the reactive term changes sign. Exact phasor calculation is preferred when voltage drops are significant.

6. Autotransformers

An autotransformer has one continuous winding with a common portion shared by input and output. It transfers part of the power conductively and part inductively. For an ideal step-down autotransformer with high-side voltage VH and low-side voltage VL,

Scommon/Stotal = (VH − VL)/VH

and the copper and core material can be substantially reduced compared with a two-winding transformer of the same rating.

Advantages include high efficiency, smaller size, lower cost, and better regulation. Limitations include absence of electrical isolation, higher fault current, and an unsafe output if the common conductor is improperly connected. Autotransformers are used for motor starting, voltage control, and interconnection of systems with closely related voltages. A variac is a variable autotransformer and must not be treated as an isolation device.

7. Three-Phase Transformers

Three single-phase units or a common three-limb core may form a three-phase transformer. Common connections are:

ConnectionTypical characteristic
Y–YNeutral access; sensitive to unbalanced loads and triplen harmonics unless a suitable neutral or tertiary exists
Δ–ΔHandles unbalance relatively well; can continue at reduced capacity as open-delta in special circumstances
Y–ΔProvides a 30° phase displacement and a path for triplen harmonic currents in the delta
Δ–YCommon in distribution; provides a neutral on the star side and 30° displacement

For a balanced three-phase system,

S = √3 VL IL

where VL and IL are line voltage and line current. In a star connection, VL = √3 Vphase and IL = Iphase. In a delta connection, VL = Vphase and IL = √3 Iphase. The exact phase displacement depends on the connection and terminal convention; it must be identified before paralleling transformers.

8. Harmonics and Inrush Current

The nonlinear magnetization curve produces excitation-current harmonics, especially the third harmonic and other triplen components. In three-phase systems, triplen currents can circulate in a delta or flow in a neutral. Excessive harmonics increase heating, acoustic noise, losses, and relay errors. K-rated transformers, derating, harmonic filters, and suitable winding arrangements may be required for nonlinear loads.

Inrush current occurs when a transformer is energized. Residual core flux and the switching angle can drive the core into saturation, producing a transient current many times the rated current. Inrush is not necessarily evidence of a short circuit. Differential protection therefore uses harmonic restraint or blocking, while overcurrent protection must be coordinated to avoid nuisance tripping. Controlled switching, residual-flux management, and pre-insertion impedance can reduce inrush.

9. Parallel Operation

Transformers may operate in parallel to increase capacity and improve continuity, but essential compatibility conditions apply:

  • equal voltage ratios and compatible tap settings;
  • identical polarity;
  • the same phase sequence and phase displacement for three-phase units;
  • compatible percentage impedance and X/R ratio;
  • matching frequency and suitable rated voltage;
  • compatible vector group and grounding arrangement.

If voltage ratios differ, circulating current flows even without an external load. If impedances differ, load sharing is unequal. For two transformers with common secondary voltage and impedances Z₁ and Z₂, approximate current sharing is inversely proportional to impedance magnitude:

I₁/I₂ ≈ |Z₂|/|Z₁|

This relation assumes compatible phase angles and neglects tap and nonlinear effects.

10. Transformer Condition Assessment

Condition assessment combines visual inspection, electrical testing, thermal observation, and—where justified—chemical analysis. Important indicators include:

  • insulation resistance and polarization index;
  • winding resistance and ratio measurements;
  • excitation current and no-load loss;
  • dielectric dissipation factor or tan δ;
  • oil dielectric strength, moisture, acidity, and dissolved-gas analysis for oil-filled units;
  • thermography of bushings, connections, and radiators;
  • unusual sound, vibration, leakage, corrosion, or bushing damage.

A single abnormal reading should not automatically determine a replacement decision. Results should be compared with manufacturer data, historical trends, phase-to-phase symmetry, temperature, loading, and applicable standards. Testing personnel must follow institutional procedures and standards such as those issued by IEC or IEEE; the applicable edition and equipment class must be confirmed rather than assumed.

Illustrative Case Study: Distribution Transformer Investigation

Background. A 500 kVA, 11 kV/415 V distribution transformer develops an audible increase in noise and a gradual rise in top-oil temperature at its usual load.

Problem. The operator must determine whether the cause is overload, harmonic current, poor cooling, loose mechanical components, or insulation deterioration.

Analysis. Load records show only 70% rated current but a high concentration of rectifier loads. Thermography identifies a warm low-voltage termination. Harmonic measurements show substantial triplen current in the neutral. Oil tests do not show a rapid increase in combustible gases, and winding-resistance measurements are symmetrical.

Approach. The termination is isolated and retorqued according to the manufacturer’s procedure. Neutral and phase currents are measured, ventilation is inspected, and the transformer is assessed using harmonic-aware loading guidance. The distribution arrangement is reviewed to determine whether a delta tertiary or a transformer with an appropriate K-factor is required.

Outcome. The connection temperature decreases after corrective maintenance, but harmonic heating remains. The operator schedules load redistribution, improves monitoring, and evaluates replacement capacity rather than treating the initial symptom as a winding fault.

Learning points. Diagnosis should integrate electrical, thermal, mechanical, and historical evidence. A low average load does not guarantee low thermal stress when harmonics or poor connections are present. Safety isolation, competent personnel, and documented acceptance criteria are essential.

11. Practical Best Practices and Limitations

Laboratory results are influenced by instrument accuracy, waveform distortion, temperature, lead resistance, contact quality, and assumptions such as negligible no-load copper loss. Students should state these assumptions in reports, include units, retain significant figures consistent with instrument accuracy, and compare calculated parameters with nameplate data.

Never short a current transformer secondary while energized unless the equipment is specifically designed for that procedure, and never leave a voltage transformer secondary open when the design prohibits it. Transformer oil, insulation materials, and electrical fields also create environmental and occupational hazards. Used oil and contaminated materials require controlled disposal. AI-based monitoring can assist with anomaly detection and trend analysis, but it must not replace protection systems, engineering judgment, or verified test procedures. Models require quality historical data and can produce false alarms when operating conditions change.

Chapter Summary

Magnetic circuits provide the flux framework underlying transformer operation. Flux is established by magnetomotive force against reluctance, while core material behavior introduces hysteresis, eddy-current loss, and saturation. Faraday’s law relates flux, frequency, turns, and induced emf. Real transformers are represented by equivalent circuits containing winding resistance, leakage reactance, core-loss resistance, and magnetizing reactance.

Open-circuit tests estimate excitation and core-loss parameters; short-circuit tests estimate series impedance and full-load copper loss. These parameters support calculations of efficiency, maximum-efficiency conditions, and voltage regulation. Polarity testing is essential for safe series connection and parallel operation. Autotransformers offer economy and high efficiency but do not provide isolation. Three-phase connections determine voltage relationships, neutral availability, harmonic behavior, and phase displacement. Harmonics, inrush, unequal impedance, and poor condition monitoring are important practical concerns. Reliable condition assessment combines electrical, thermal, mechanical, chemical, historical, and safety evidence.

Key Terms

Magnetic flux: The total magnetic field through a surface, measured in webers.

Flux density: Magnetic flux per unit area, measured in tesla.

Magnetomotive force: The product of turns and current that drives flux.

Reluctance: Opposition offered by a magnetic path to flux.

Permeability: A material’s ability to support magnetic flux.

Hysteresis: Energy-loss behavior caused by cyclic magnetization.

Saturation: A region where increases in magnetizing force produce little additional flux.

Leakage flux: Flux linking one winding but not the other.

Turns ratio: The ratio of primary to secondary turns.

Polarity: The instantaneous voltage relationship between winding terminals.

Equivalent circuit: A circuit model representing transformer losses and reactances.

Open-circuit test: A test used mainly to determine core-loss and excitation parameters.

Short-circuit test: A test used mainly to determine series impedance and copper loss.

Voltage regulation: The load-related change in secondary voltage.

Autotransformer: A transformer using a portion of one continuous winding in common.

Inrush current: A transient energization current caused mainly by core saturation.

Harmonics: Frequency components at integer multiples of the fundamental frequency.

Vector group: A designation of three-phase transformer winding connection and phase displacement.

Dissolved-gas analysis: Examination of gases dissolved in transformer oil to indicate faults.

Review Questions

Short Answer Questions

  1. Define reluctance and state its SI unit.
  2. Why are transformer cores laminated?
  3. What information is obtained from an open-circuit test?
  4. State two essential conditions for parallel transformer operation.
  5. Why does an autotransformer not provide electrical isolation?

Long Answer Questions

  1. Explain the construction of a transformer equivalent circuit and the physical meaning of each element.
  2. Describe the procedure, assumptions, and calculations of open-circuit and short-circuit tests.
  3. Compare Y–Y, Δ–Δ, Y–Δ, and Δ–Y three-phase connections.
  4. Explain transformer efficiency and voltage regulation, including the effects of load power factor.
  5. Discuss the causes, consequences, and mitigation of harmonics and inrush current.

Analytical / Application Questions

  1. A transformer short-circuit test gives Vsc = 24 V, Isc = 8 A, and Psc = 96 W. Calculate Zeq, Req, and Xeq referred to the test side.
  2. Two transformers are operated in parallel with equal voltage ratios. Their impedances are 0.04 pu and 0.06 pu. Which transformer carries the larger share of load, and why?
  3. A distribution transformer has normal average loading but overheats during operation of many rectifier loads. Propose a measurement and diagnostic plan, and identify at least three possible corrective actions.

Multiple Choice Questions with Answers

Question 1

Which quantity is the magnetic-circuit analogue of electrical resistance?

A. Permeability

B. Reluctance

C. Flux density

D. Magnetizing current

Correct Answer: B. Reluctance

Question 2

For a sinusoidal transformer flux, the rms induced emf is given by which expression?

A. E = 2πfNΦₘ

B. E = 4.44fNΦₘ

C. E = NIℜ

D. E = Φₘ/(fN)

Correct Answer: B. E = 4.44fNΦₘ

Question 3

During a transformer open-circuit test, the measured wattmeter power is primarily the

A. Full-load copper loss

B. Leakage-reactance loss

C. Core loss

D. Load power

Correct Answer: C. Core loss

Question 4

A short-circuit test measures Vsc = 12 V and Isc = 4 A. What is the equivalent impedance magnitude?

A. 0.33 Ω

B. 3 Ω

C. 16 Ω

D. 48 Ω

Correct Answer: B. 3 Ω

Question 5

If a transformer has turns ratio a = N₁/N₂ = 5, a secondary resistance of 0.20 Ω referred to the primary is

A. 0.008 Ω

B. 0.04 Ω

C. 1 Ω

D. 5 Ω

Correct Answer: C. 1 Ω

Question 6

Approximate maximum transformer efficiency occurs when

A. Exciting current is zero

B. Copper loss equals core loss

C. Voltage regulation is zero

D. Load power factor is zero

Correct Answer: B. Copper loss equals core loss

Question 7

Which transformer connection commonly provides a neutral on the secondary distribution side?

A. Δ–Δ

B. Y–Δ

C. Δ–Y

D. Open-delta only

Correct Answer: C. Δ–Y

Question 8

The principal cause of transformer inrush current is

A. Permanent short-circuit impedance

B. Core saturation immediately after energization

C. Reduced winding resistance at high temperature

D. Balanced three-phase loading

Correct Answer: B. Core saturation immediately after energization

Question 9

Which feature distinguishes an autotransformer from a conventional two-winding transformer?

A. It operates only on direct current

B. It has no magnetic core

C. Part of its winding is common to input and output

D. It cannot change voltage

Correct Answer: C. Part of its winding is common to input and output

Question 10

If two parallel transformers have compatible ratios and impedances of 0.04 pu and 0.08 pu, the transformer with 0.04 pu impedance will approximately carry

A. Half as much current

B. The same current

C. Twice as much current

D. Four times as much current

Correct Answer: C. Twice as much current

Electrical Machines & Power Systems Laboratory
Chapter 3 of 15